Plan Review Notes
Plan Review Notes For Permit 02102193
Permit Number 02102193
Review Stop R
Sequence Number 1
Notes
Date Text
2002-12-31 00:00:00CHECKLIST:
 1-ARCHITECT TO PROVIDE ALL INFORMATION
 REQUIRED BY SECTION 1606.1.7 FBC 2001.
 (NOTE: NEED TO LIST ALL 5 ITEMS)
 2-PROVIDE AT LEAST ONE COMPLETE BATHROOM
 WITH A DOOR THAT ALLOWS 29" MIN. CLEAR
 OPENING. SEC. 11-11 FBC 2001.
 3-CLARIFY SIZE OF BEDROOM EGRESS WINDOWS
 WHAT IS A SH2853 AS CALLED ON FLOOR
 PLANS. CLARIFY/REVISE AS REQUIRED. SEE
 PLANS, RIGHT ELEVATION.
 4-SPECIFY IN PLANS ALL AREAS TO HAVE
 SAFETY GLASS AS REQUIRED BY SECTION
 2405.2 FBC 2001. ALSO, SAFETY GLASS TO
 PASS TEST REQUIREMENTS OF SECTION
 2405.1 FBC 2001.
 5-SIZE OF DOORS & WINDOWS CALLED ON PLAN
 DON'T MATCH SIZE SHOWN ON PLANS AND
 ELEVATIONS. EG: SEE SIZE SPECIFIED FOR
 SLIDING GLASS DOORS AT REAR ELEVATION.
 **NOTE: ALSO, SEE SITE SPECIFIC ENGINEE-
 RING INFORMATION FOR FIXED WINDOWS AND
 REVISE DRAWINGS AS REQUIRED TO MATCH
 THOSE. EG: HER BATH SHOWS BUTT GLAZING
 AND PRODUCT APPROVAL SHOWS STRUCTURAL
 MULLIONS. WHICH ONE IS CORRECT?
 6-REVISE DETAIL 11 OF SHEET A9 TO MATCH
 FIREPLACE CONSTRUCTION SHOWN ON PLANS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC
 **NOTE: SPECIFY ON EXTERIOR ELEVATIONS
 THE MIN. CHIMNEY HEIGHTS REQUIRED BY
 SEC. 2804.2.4 FBC 2001.
 7-PROVIDE GENERAL SPECIFICATIONS FOR
 FIREBLOCKING AT ALL CONCEALED SPACES
 AS REQUIRED BY SEC. 2305.1.4 FBC 2001.
 8-SPECIFY SUPPORTS FOR WWM IN CONCRETE
 SLAB AS REQUIRED BY SEC. 1090.3 FBC.
 9-PROVIDE COMPLETE DETAILS/SPECS FOR
 INSTALLATION OF CEILINGS AT FRONT AND
 REAR PORCHES. SPECIFY ALL FASTENERS &
 SPACING. SEE ASTM C926 AND ASTM C-1063
 AS REQUIRED BY SEC. 2504.2 FBC 2001.
 10-REVISE STRUCTURAL BUCK FOR SWING DOOR
 SEE SEC. 1707.4.4.2 FBC 2001.
 11-NEED RECORDED NOTICE OF COMMENCEMENT.
 12-PROVIDE PRODUCT APPROVAL FOR:
 A)ENTRY DOORS ASSEMBLY AS SHOWN ON PLANS
 B)STOREFRONT GLAZING SYSTEM: ARCHITECT
 TO SIGN, SEAL & DATE SITE SPECIFIC
 FORM AS WELL. PROVIDE HIS INFORMATION
 AS REQUIRED BY CHAPTER 481 FL STATUTES
 AND IDENTIFY THE JOB SITE.
 **ALSO, PROVIDE THE PRODUCT APPROVAL #
 00-1220.5 FOR STOREFRONT SYSTEMS AS
 REFERENCED ON THIS FORM.
 C)SITE SPECIFIC FIXED WINDOWS PRODUCT
 APPROVAL NEEDS TO BE SIGNED, SEALED
 AND DATE BY ARCHITECT AS WELL. PROVIDE
 HIS INFORMATION AND IDENTIFY JOB SITE.
 D)GARAGE DOORS PRODUCT APPROVAL NEED
 LEGIBLE APPROVED DRAWINGS.
  
 13-PROVIDE COMPLETE INFO. FOR STORM SHU-
 TTERS OR APPLY FOR A SEPARATE PERMIT.
 CITY IMPLEMENTATION STANDARD FOR HURRI
 CANE MISSILE IMPACT PROTECTION.
 14-LIBRARY ROOM MAY BE USED AS SLEEPING
 ROOM. NEED TO PROVIDE EGRESS WINDOW OR
 AS PER CITY BUILDING OFFICIAL INTERPRE
 TATION CLEARLY WRITE ON PLANS THAT
 THIS ROOM SHALL NOT BE USED FOR
 SLEEPING PURPOSES.
 15-SEE PLANS FOR ADDITIONAL COMMENTS AND
 PLEASE RETURN REVIEWED SET AFTER THE
 CORRECTIONS ARE DONE TO THE ORIGINAL
 CAD DRAWINGS TO EXPEDITE THE REVIEW.
 ALSO, RETURN DWGS THAT ARE ALREADY
 STAMPED AND APPROVED TO AVOID SENDING
 DWGS BACK AND FORTH TO OTHER TRADES.