| Plan Review Notes For Permit 02102193 |
| Permit Number |
02102193 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-12-30 00:00:00 | *************** UNSAT ************** | | | | | | 1)NOTE: PLEASE CLARIFY GROUPING OF MAINS | | | PER 230-72. METER ONLY SHOWSONE MAIN | | | NEXT TO IT. | | | | | | 2)NOTE: PLEASE NOTE PANELS ARE SHOWN AS | | | 200MCBAND RISER SHOWS AS 150A MLO? | | | PLEASE CORRELATE. | | | | | | 3)NOTE: PLEASE SEE MISSING FOOTER STEEL | | | PER 250-50 | | | | | | 4)NOTE: PLEASE CLARIFY PADDLE FANS | | | SHOWN OFF PANEL SCHEDULE. | | | | | | 5)NOTE: PLEASE RE-CONFIGURE LOAD | | | CALCULATIONS, PLEASE NOTE #`S DO NOT | | | CORRELATE W/ SUBMITTED PANEL SCHEDULES. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVEIW | | | 561-659-8096 EXT 8372 |
|