| Date |
Text |
| 2002-11-14 00:00:00 | DENIED: | | | | | | CLARIFY ACCESS FOR MAINTENANCE, SERVICE | | | OR REPLACEMENT OF THE AHU'S AND ITS | | | COMPONENTS.2001FBC(M) 306.1 | | | | | | INDICATE ELEVATION OF AHU'S. | | | | | | PROVIDE MANUFACTURER SUBMITTAL DATA ON | | | THE STANDS FOR THE CONDENSER UNITS. | | | SHOW COMPLIANCE WITH 2001 FBC TABLE | | | 1511.7 - MINIMUM HEIGHT REQUIREMENT FROM | | | ROOF SURFACE.SHOW ACCESS TO CONDENSER | | | UNITS LOCATED ON THE ROOF. | | | | | | ADDITIONAL PERMIT REQUIRED FOR WALK IN | | | COOLERS OR FREEZERS. PROVIDE SUBMITTAL | | | DATA FROM MANUFACTURER. SHOULD CONDENSER | | | UNIT BE REMOTE, SHOW LOCATION OF C.U. | | | | | | INDENTIFY CONDENSATE TERMINATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|