Plan Review Notes
Plan Review Notes For Permit 02102183
Permit Number 02102183
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-11-14 00:00:001) PLANS INDICATE THE INSTALLATION OF
 AN ADDITIONAL FIRE ALARM CONTROL PANEL.
 NO NEW ADDITIONAL FIRE ALARM PANELS
 WILL BE ALLOWED TO BE INSTALLED WITHIN
 TENANT SPACES. FIRE ALARM EQUIPMENT MUST
 BE CONNECTED WITHIN THE TENANT SPACE
 TO THE BASE BUILDING FIRE ALARM PANEL.
 EXISTING SUB FIRE ALARM CONTROL PANELS
 HAVE CAUSED SIGNIFICANT PROBLEMS.
 PLEASE DELETE THIS ITEM FROM THE
 PLANS AND REVISE AS NECESSARY.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910