| 2003-02-07 00:00:00 | ************** UNSAT ************ | | | | | | PLANS ARE BEING SUBMITTED COMPLETED AND | | | HAVE THE FOLLOWING COMMENTS. | | | | | | 1)NOTE: PLEASE CORRELATE RISER AND PANEL | | | SCHEDULE. ONE SHOWS 100A PANEL AND OTHER | | | SHOWS 200A? | | | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | NEW DISC AND PANEL. 110-9/215-5 | | | | | | 3)NOTE: PLEASE INCLUDE CWP AS PART OF | | | THE GROUNDING SYSTEM AT BLDG. 250-50 | | | | | | 4)NOTE: PLEASE SHOW LOAD CALCULATIONS, | | | SOME CONN LOADS SHOWN ON PANEL SCHEDULE | | | EXCEED 100A RATING OF PANEL, SOME ARE | | | SHOWN UNDER?? PLEASE SUBMIT A LOAD | | | CALC PER 220-3,10,11,13 ETC, ANY CONTIN- | | | UOUS LOADS AT 125%. 215-3,230-42 ETC | | | PLEASE ADJUST SERVICE AS NEEDED BY LOAD. | | | | | | 5)NOTE: PLEASE SEE MECH PLAN, AHU HEAT | | | IS SHOWN AT 5KW, ELECTRICAL PANEL/LOADS | | | DO NOT CORRELATE, ELEC SHOWS AHU AT 13A | | | AND #12 AWG ON 2P-20??? PLEASE ALSO SEE | | | COMP UNIT SHOWN AS 2-P35A ON #12?? | | | PLEASE SEE 424-3 FOR OCP OF HEAT. MIN | | | 125% OF LOAD. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|