| Plan Review Notes For Permit 02101904 |
| Permit Number |
02101904 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-12-26 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | 1) SHT P-1 WASTE AND VENT RISER DOES NOT | | | REFLECT FLOOR PLAN. DRINKING FOUNTAIN | | | NOT SHOWN ON RISER. | | | 2) SHT P-1 WASTE & VENT RISER, VENT REQ- | | | UIRED FOR SHOWER & FLOOR SINK, AND VENT | | | REQUIRED FOR SINK IN PRO SHOP. | | | 3) SHT P-1 INDIRECT WASTE SHALL DRAIN | | | TO A FLOOR SINK. 802.3 - FLOOR DRAIN IS | | | NOT AN APPROVED WASTE RECEPTOR. | | | 4) SHT P-1 WATER RISER DOES NOT REFLECT | | | FLOOR PLAN. DRINKING FOUNTAIN NOT SHOWN | | | ON WATER RISER DIAGRAM. | | | 5) RPZ BACKFLOW REQUIRED ON WATER SERV. | | | 6) SHT P-1 WATER HEATER DETAIL, THERMAL | | | EXPANSION CONTROL REQUIRED PER 607.3.2. | | | PLEASE SHOW ON DETAIL | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|