| Plan Review Notes For Permit 02101904 |
| Permit Number |
02101904 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-12-24 00:00:00 | DENIED: | | | | | | 1.PLEASE PROVIDE ENERGY & COOLING LOAD | | | CALCULATION AS PER 2001 FBC CHAPTER | | | 13 SECTION 400.0 & 407.1.ABCD.1. | | | | | | 2.PLAN SHEET M1 GENERAL HVAC NOTES #2, | | | INDICATES CONDENSING UNIT SHALL BE | | | A 1.5 TON UNIT.EQUIPMENT SCHEDULE | | | INDICATES A 3 TON. PLEASE CORRELATE. | | | | | | 3.PLEASE CLARIFY R/A LOUVERD DOOR INTO | | | THE STORAGE ROOM. AS PER 2001 FBC(M) | | | 602.1 RETURN AIR PLENUMS SHALL BE | | | LIMITED TO UNINHABITED SPACES, THE | | | STORAGE ROOM IS NOT CONSIDERED AN | | | UNINHABITED SPACE. | | | | | | 4.CONDENSATE SHALL DISCHARGE A MINIMUM | | | OF 12" AWAY FROM THE BUILDING | | | STRUCTURE, 2001 FBC 1503.4.4. | | | | | | 5.PROVIDE OUTSIDE AIR CALCULATIONS | | | AS PER 2001 FBC(M) TABLE 403.3. | | | | | | 6.EXHAUST FAN SCHEDULE INDICATES FANS | | | ARE IN THE CLASS RMS? PLAN INDICATES | | | EXHAUST FANS ARE IN THE RESTROOMS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|