| Plan Review Notes For Permit 02101904 |
| Permit Number |
02101904 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-12-09 00:00:00 | ******** UNSAT ********* | | | | | | 1)NOTE: PLEASE SHOW ALL CIRCTUIING ON | | | PLANS AND CORRELATE WITH A SUBMITTED | | | PANEL.215-5 | | | | | | 2)NOTE: PLEASE NOTE, NO LOAD CALCULATION | | | -S/ PANEL SCHEDULE WERE SUBMITTED. | | | 215-5 | | | | | | 3)NOTE: PLEASE SHOW TRACK LIGHTING CALCS | | | PER 220-12B | | | | | | 4)NOTE: PLEASE NOTE THERE IS NO EQUIP- | | | -MENT GROUND BETWEEN METER AND MAIN. | | | 250-24, PLEASE ALSO NOTE GROUNDING | | | CONDUCTOR SHOWN, IS SHOWN AS #5. PLEASE | | | NOTE #5 IS NOT A STANDARD SIZE PER AWG. | | | | | | 5)NOTE: PLEASE PROVIDE GROUNDING SYSTEM | | | AT BLDG. 250-50/ 250-32 | | | | | | PLEASE NOTE PLANS NEED TO BE COMPLETED | | | FOR COMPLETE REVIEW. IF THERE ARE ANY | | | QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|