| Date |
Text |
| 2002-12-03 00:00:00 | SHEET SP1 RE: THE HANDICAP PARKING |
| | SPACES.PLEASE PROVIDE SPECIFIC DESIGN |
| | INFORMATION, DO NOT QUOTE THE CODE |
| | SECTION.ALSO, THE SITE PLAN DOES NOT |
| | HAVE ANY DIMENSIONS LOCATING THE |
| | PROPOSED CONSTRUCTION ON THE PROPERTY. |
| | |
| | THE PLANS DO NOT INDICATE THE ROOF SLOPE |
| | OR THE WIND PRESSURE ZONES. |
| | |
| | PLEASE DEMONSTRATE HOW THE GABLE ENDS OF |
| | THE ROOF WILL MEET THE "STRUCTURALLY |
| | CONTINUOUS" REQUIREMENT OF FBC 2313.4.1. |
| | |
| | PLEASE PROVIDE A SPECIFIC METHOD OF |
| | INSTALLATION FOR THE "FIBER CEMENT |
| | PANELS" AS DEFINED BY THEIR NER 405 |
| | LISTING. |
| | |
| | INDICATE THE ATTIC ACCESS REQUIRED BY |
| | FBC 2309.6. |
| | |
| | SHOW A STRUCTURAL DETAIL FOR THE |
| | TRANSITION/TERMINATION OF THE 8X16 TIE |
| | BEAM AT ELEVATION 109'-4" INTO THE CMU |
| | PRACTICE WALL. |
| | |
| | THE SPECIFICATIONS DECLARE AN F'M OF |
| | 2000 PSI FOR THE MASONRY AND THE |
| | STRUCTURAL SHEET CALLS OUT 1500 PSI. |
| | PLEASE CLARIFY THE INTENT.THE |
| | SPECIFICATIONS ARE NOT SEALED BY THE |
| | ENGINEER. |
| | |
| | IF THE TEST REPORTS AND OR THE NOTICE OF |
| | ACCEPTANCE INFORMATION FOR THE DOORS |
| | WINDOWS AND ROOF COVERING ARE NOT |
| | INCLUDED WITH THE PERMIT APPLICATION, A |
| | SEPARATE PERMIT, FEES AND PLANS WILL BE |
| | REQUIRED. |
| | |
| | SHOW HOW THE GLAZED AREAS OF THE |
| | BUILDING EXTERIOR WILL RESIST HURRICANE |
| | MISSILE IMPACT.SEE FBC 1606.1.4. |
| 2002-11-05 00:00:00 | TO ZONING BOX./WRT. |