| Plan Review Notes For Permit 02101893 |
| Permit Number |
02101893 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-05-21 00:00:00 | ************ UNSAT ****************** | | | | | | 1)NOTE; PLEASE CORRECT MAIN PANEL SHOW- | | | ING10 CIERCUITS TO SUB PANEL. | | | PLEASE SEE SUB PANEL, SHOWS 10 CIRCUITS | | | AS 2P60A AND #6? | | | | | | 2)NOTE: PLEASE CORRELATE AWG FOR FEEDERS | | | ON RISER DIAGRAM. SHOWS #6`S TO 200A | | | PANEL AND SHOWS 2/0`S TO 60A PANEL? | | | | | | 3)NOTE: PLEASE SEE THAT SD IS STILL | | | SHOWN IN KITCHEN. NOT PERMITTED UNDER | | | NFPA-72 8-1.4.2. | | | | | | THESE ITEMS WERE REDLINED ON ORIG PLANS | | | AND HAVE NOT BEEN ADDRESSED SINCE ORIG | | | REVIEW. PLEASE SUBMIT THE ABOVE FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|