2003-05-21 00:00:00************ UNSAT ******************
  
 1)NOTE; PLEASE CORRECT MAIN PANEL SHOW-
 ING10 CIERCUITS TO SUB PANEL.
 PLEASE SEE SUB PANEL, SHOWS 10 CIRCUITS
 AS 2P60A AND #6?
  
 2)NOTE: PLEASE CORRELATE AWG FOR FEEDERS
 ON RISER DIAGRAM. SHOWS #6`S TO 200A
 PANEL AND SHOWS 2/0`S TO 60A PANEL?
  
 3)NOTE: PLEASE SEE THAT SD IS STILL
 SHOWN IN KITCHEN. NOT PERMITTED UNDER
 NFPA-72 8-1.4.2.
  
 THESE ITEMS WERE REDLINED ON ORIG PLANS
 AND HAVE NOT BEEN ADDRESSED SINCE ORIG
 REVIEW. PLEASE SUBMIT THE ABOVE FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  