| Plan Review Notes For Permit 02101889 |
| Permit Number |
02101889 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-11-19 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION,MAKE ANY NECESSARY CHANGES | | | TO THE PLANS AND RESUBMIT FOR REVIEW. | | | | | | 1} PLEASE LIST THE REQ'D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG.,ON THE PANEL | | | SCHEDULE. | | | | | | 2} NOTE THE LAUNDRY CIRCUIT IS TO BE | | | CALCULATED AT 1500 VA PER 220-16. | | | | | | 3} PLEASE GIVE A PANEL SCHEDULE FOR | | | PANEL"C",AND GIVE LOCATION OF SAME. | | | | | | 4} THE SMOKE DETECTOR IN THE KITCHEN IS | | | IN VIOLATION OF 8-1.4.2 NFPA-72.(A HEAT | | | DETECTOR WOULD BE PERMISSIBLE). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT. 8392 |
|