Plan Review Notes
Plan Review Notes For Permit 02101889
Permit Number 02101889
Review Stop E
Sequence Number 1
Notes
Date Text
2002-11-19 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE ANY NECESSARY CHANGES
 TO THE PLANS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.,ON THE PANEL
 SCHEDULE.
  
 2} NOTE THE LAUNDRY CIRCUIT IS TO BE
 CALCULATED AT 1500 VA PER 220-16.
  
 3} PLEASE GIVE A PANEL SCHEDULE FOR
 PANEL"C",AND GIVE LOCATION OF SAME.
  
 4} THE SMOKE DETECTOR IN THE KITCHEN IS
 IN VIOLATION OF 8-1.4.2 NFPA-72.(A HEAT
 DETECTOR WOULD BE PERMISSIBLE).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392