Plan Review Notes For Permit 02101888
Permit Number 02101888
Review Stop B
Sequence Number 1
Notes
Date Text
2002-12-09 00:00:00 
  
 *** ISSUED PERMIT***
 -PLAN REVIEW HISTORY-
  
 PERMIT# 02101888
 ADDRESS: 3065 SANTA MARGARITA RD
 CONT: DOUBLE D BLDG
 TELL # (954)796-0777
  
 THE ATTACHED COMMENTS ARE PART OF THE
 PERMIT AND PLAN REVIEW PACKAGE AND ARE
 NOT TO BE REMOVED FROM THE ISSUED SET OF
 PLANS.104.2.1.2 ADMINISTRATIVE CODE.
  
 ******PROVISO******
 1) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED.MISSING REPORTS:
 A) SOLID CORE FRONT DOORS
 B) FRENCH DOORS W/ GLAZING
 REPORTS DUE SUBMITTED TO THIS OFFICE BE-
 FORE BUCK INSPECTION (119).
  
 2) GLASS BLOCK ON ZERO LOT LINE SIDE
 REQUIES 1 HR RATING PRODUCT TESTING
 REPORT FOR FIRE RATING TO THIS OFFICE
 BEFORE BUCK INSPECTION (119).
  
 3)SITE SPECIFIC ENGINEERING (PRODUCT
 APPROVAL) REQUIRES THE WET SIGNATURE,
 DATE AND EMBOSSED SEAL OF THE ENGINEER
 CERTIFYING THE PRODUCT AND SIGNATURE
 AND SEAL OF THE DESIGN PROFESSIONAL
 OF RECORD.
  
 W. P. B. MISSLE IMPACT PROTECTION STAND-
 ARD, SITE SPECIFIC REQUIREMENTS ARE NOT
 MET, SEE ITEM # 17 OF STANDARD, A SEPER-
 ATE PERMIT SHALL BE REQUIRED WITH SEPER-
 ATE FEES ANS REVIEWS.
 BUILDING PLAN REVIEW
 JIM WITMER