Plan Review Notes
Plan Review Notes For Permit 02101887
Permit Number 02101887
Review Stop B
Sequence Number 1
Notes
Date Text
2002-12-09 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT:02101887
 ADD: 3177 SANTA MARGARITA RD
 CONT: DOUBLE R BLDG CORP
 TEL: (954)796-0777
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 A PRELIMINARY GEOTECHNICAL EVALUATION
 SECTION 7. THE REPORT INDICATES THAT IN
 SEC 4.3 BUILDING FOUNDATIONS: ALL FINAL
 DESIGNS SHOULD BE BASED ON A MORE COM-
 PREHENSIVE STUDY ONCE THE BUILDING
 LOCATIONS AND STRUCTURAL LOADS ARE
 FINALIZED.
  
 THE REPORT GIVEN TO THE CITY ALSO ISN'T
 SIGNED NOR SEALED!
  
  
 3)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORTS:
 A) HORIZONTAL MULLIONS, REPORT SUBMITT-
 ED IS FOR VERTICAL USAGE ONLY, SEE
 LIMITATIONS.
 B) FRONT ENTRY DOOR
 C) FRENCH DOORS W/ GLAZING
 D) STORM SHUTTERS MISSING KEY PLAN &
 INSTALATION SCHEDULE
  
 4)SITE SPECIFIC ENGINEERING (PRODUCT
 APPROVAL) REQUIRES THE WET SIGNATURE,
 DATE AND EMBOSSED SEAL OF THE ENGINEER
 CERTIFYING THE PRODUCT AND SIGNATURE
 AND SEAL OF THE DESIGN PROFESSIONAL
 OF RECORD.BROWARD REPORTS REQUIRE SITE
 SPECIFIC ENGINEERING, USING THE CRITERIA
 SET FORTH IN W.P.B. LARGE MISSLE
 STANDARD. BOTH THE CERTIFICATE OF
 COMPLIANCE AND THE INSTALATION AFFIDAVAT
 IS TO BE ON THE APPROVED FORMS PROVIDED
 BY THE CITY OF WEST PALM BEACH.
  
 4) STORM SHUTTER SCHEDULE:
 FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 5) TABLE 600 ZERO-LOT LINE REQUIRES THE
 WALL TO BE 1 HR RATED, THIS INCLUDDES
 THE GLASS BLOCK, NO INFORMATION PROVIDED
  
 6) ON C1 PLAN NOTES #11 INDICATES HVHZ
 ZONE! W.P.B. IS NOT LOCATED IN SUCH A
 ZONE ONLY DADE/ BROWARD COUNTIES. STORM
 SHUTTERS ARE STILL REQUIRED, 140 MPH
 WIND ZONE.
  
 7) ON C1 FRAMING NOTE # 15 SPECIFIES
 FASTENERS FOR HIGH RIB LATH @ 6" O.C.,
 ASTM C-1063 RIB LATH SHALL BE ATTACHED @
 4" O.C. (AT EACH RIB).
  
 8) 2111.1.9 COUNTY AMENDMENTS/ FBC
 REQUIRE A 1.5" RECESS (WATER STOP)
 WHERE EXTERIOR WALL (CMU) BEAR ON A CON-
 CRETE FLOOR SURFACE.SEE TYPICAL WALL
 SECTIONS A-1 & A-6.
  
 9) PLANS INDICATETHE USE OF A "F12"
 FOOTING,MISSING IN SCHEDULE.
  
 10) FOUNDATION SCHEDULE MISSING THE
 FOOT & INCH DESIGNATIONS.
  
 11) ROOF NAILING ZONE # 3, WHEN THE MEAN
 ROOF HEIGHT IS GREATER THAN 25', ZONE 3
 REQUIRES RING SHANK NAILS.
  
 12) DISCREPENCIES, PLEASE CORRECT:
 A) DETAIL# 8 ON SHEET 7 IS INDICATED AS
 2ND STORY FRAMING WHILE IT IS BLOCK!
 B) DETAIL# 9 SHEET 7 SAME AS ABOVE,
 FRAME VS. BLOCK!
 C) DETAIL 13 ON A-7 IS NOT INDICATED ON
 THE FRAMING PLAN, PROBABLY SHOULD BE
 DETAIL# 8 SHEET 7.
 D) SHEET# 8 DETAIL 12 AS INDICATED ON
 THE 2ND FLOOR FRAMING PLAN MISSING
 DETAIL, DETAILS START WITH # 15.
  
 13)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026