| Plan Review Notes For Permit 02101839 |
| Permit Number |
02101839 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-03-17 00:00:00 | 1) DIMENSIONS ON SITE PLAN DON'T MATCH | | | FLOOR PLAN | | | 2) MISSING PRODUCT APPROVAL ON GARAGE | | | DOORS AS WELL AS SWING DOORS | | | 3) IF OWNER WANTS ANY WINDOWS -WILL NEED | | | PRODUCT APPROVALS FOR THESE AS WELL | | | 4) TRUSS DRAWINGS ARE ALSO NEEDED - BOTH | | | FOR FLOOR AND ROOF SYSTEMS | | | 5) HAVE ARCH. REDRAW EVERYTHING AS TO | | | WHAT IS ACTUALLY IN THE FIELD--SIZE OF | | | SLAB, THEN DIMENSIONS OF WALLS WITH | | | SIZE OF OPENINGS | | | 6) DENSITY REPORTS FOR SLAB AREA | | | 7) TERMITE TREATMENT VERIFICATION | | | 8) ADDITIONAL FEES $ 600.00 |
|