2002-11-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SANITARY RISER DIAGRAM DOES NOT MEET
 CODE.
 2) NO DRY HORIZONTAL VENTS ALLOWED SEC.
 905.3. (SEE VENT AFTER WATER CLOSET.
 3) SHOWER NOT VENTED.
 4) WATER CLOSET DOUBLE TRAPPED. TRAP
 UNDER SLAB NOT REQUIRED. W/C HAS INTER-
 NAL TRAP. SEC 1002.1
 5) WASH MACHINE SHALL NOT DRAIN INTO WET
 VENT FOR BATHROOM GROUP. SECTIONS 909.1,
 AND 909.2
  