| Plan Review Notes For Permit 02101817 |
| Permit Number |
02101817 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-11-09 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) SANITARY RISER DIAGRAM DOES NOT MEET | | | CODE. | | | 2) NO DRY HORIZONTAL VENTS ALLOWED SEC. | | | 905.3. (SEE VENT AFTER WATER CLOSET. | | | 3) SHOWER NOT VENTED. | | | 4) WATER CLOSET DOUBLE TRAPPED. TRAP | | | UNDER SLAB NOT REQUIRED. W/C HAS INTER- | | | NAL TRAP. SEC 1002.1 | | | 5) WASH MACHINE SHALL NOT DRAIN INTO WET | | | VENT FOR BATHROOM GROUP. SECTIONS 909.1, | | | AND 909.2 | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|