| Date |
Text |
| 2003-08-27 00:00:00 | 1) SEPARATE PLANS AND PERMITS |
| | REQUIRED FIRE ALARM SYSTEM REMODEL. |
| | |
| | 2) SEPARATE PLANS AND PEMRITS REQUIRE |
| | FOR FIRE SPRINKLER REMODEL. |
| | |
| | 3) ALL NEW SMOKE DETECTORS THAT ARE |
| | INSTALLED SHALL BE POWERED BY THE |
| | HOUSE ELECTRICAL SERVICE. THESE SMOKE |
| | DETECTORS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH MANUFACTURER'S |
| | REQUIREMENTS. |
| | |
| | 4) ALL NEW STAIRS AND RAMPS SHALL HAVE |
| | HANDRAILS ON BOTH SIDES. ALL NEW |
| | STAIRS SHALL BE AT LEAST 44" WIDE. |
| | |
| | 5) DOORS # 5 AND # 6 ARE NOT NOTED |
| | ON THE DOOR SCHEDULE. ALSO NO |
| | INFORMATION PROVIDED WITH REGARDS |
| | TO SELF-COSING DEVICES INSTALLED |
| | ON THE SLEEPING ROOM DOORS. |
| | |
| | 6) ARE ANY FIRE SPRINKLERS PLANNED TO |
| | PROTECT THE WOOD TRUSSES. |
| | |
| | 7) NO INFORMATION PROVIDED FOR INTERIOR |
| | FINISH CLASSIFICATION FOR WALLS AND |
| | CEILINGS. |
| | |
| | 8) IN SOME AREAS OF THE PLANS 5/8" |
| | DRYWALL IS NOTED. 5/8" TYPE X DRYWALL |
| | IS REQUIRED. |
| | |
| | 9) DOESN'T THE KITCHEN DOOR BLOCK THE |
| | EGRESS HALLWAY BY MORE THEN 50 %. |
| | |
| | 10) PLEASE INDICATE THE EVACUATION |
| | CAPABILITY OF THE NEW PROPOSED |
| | RESIDENTS. WILL THEY BE SLOW, PROMPT |
| | OR IMPRACTICAL. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 835-2910 |