| Plan Review Notes For Permit 02101739 |
| Permit Number |
02101739 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-02-18 00:00:00 | DENIED: | | | | | | 1.PLAN SHEET A(B)3 DETAIL 9, INDICATES | | | TENANT SEPARATION.CLARIFY FIRE | | | RESISTANCE RATING FOR THIS PARTITION. | | | SHOULD RATING BE 1 HR OR GREATER, FIRE | | | DAMPERS ARE REQUIRED AT EACH PENETRATION | | | AS PER 2001 FBC(M) 607.2.1. | | | | | | 2.AS PER 2001 FBC CHAPTER 13 SECTION | | | 407.1.ABCD.2.2.2 ZONES, HEATING AND | | | COOLING TO EACH ZONE SHALL BE CONTROLLED | | | BY INDIVIDUAL THERMOSTATIC CONTROLS | | | RESPONDING TO TEMPERATURE WITHIN THE | | | ZONE.A DWELLING UNIT IS CONSIDERED A | | | ZONE. | | | | | | 3.PROVIDE INFORMATION ON THE KITCHEN. | | | INDICATE ANY NEW EQUIPMENT.SEPARATE | | | PLANS & PERMIT REQUIRED FOR HOOD & FIRE | | | SUPRESSION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|