| 2003-02-19 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | ***NOTE:*** |
| | A NUMBER OF THE COMMENTS FROM THE |
| | PREVIOUS REVIEW HAVE NOT BEEN ADDRESSED. |
| | CHAPTER 553.80(2)(B) FLORIDA STATUTES |
| | STATES THAT A LOCAL GOVERNMENT SHALL |
| | IMPOSE A FEE OF FOUR TIMES THE FEE FOR |
| | PLAN REVIEW, IF PLANS ARE REJECTED THREE |
| | OR MORE TIMES FOR REPEATED FAILURE TO |
| | CORRECT A CODE VIOLATION. |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| | ARE NUMBERED AS PER THE BUILDING PLAN |
| | REVIEW OF 12/4/02: |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) 61G15-23.002(2)FL. ADMIN. CODE. |
| | THIS COMMENT HAS NOT BEEN ADDRESSED. |
| | PLANS SIGNED AND SEALED BY A |
| | PROFESSIONAL ENGINEER SHALL INCLUDE THE |
| | NAME AND ADDRESS OF THE ENGINEER AS WELL |
| | AS THE NAME, ADDRESS AND CERTIFICATE OF |
| | AUTHORIZATION NUMBER FOR THE ENGINEERING |
| | BUSINESS, IF APPROPRIATE. |
| | |
| | 4) FBC 311.2THE STATED R2 OCCUPANCY |
| | IS INCORRECT.PLANNING AND ZONING HAVE |
| | ADVISED THAT THEIR APPROVAL WAS BASED |
| | ON GROUP HOME OCCUPANCY WHICH WOULD BE |
| | R4 RESIDENTIAL.ALSO, THE CURRENT |
| | OCCUPATIONAL LICENSE (SUMMARY SHEET |
| | ATTACHED) IS FOR ADULT CONGREGATE LIVING |
| | FACILITY (ACLF) WHICH IS A GROUP HOME |
| | AND SO R4 RESIDENTIAL OCCUPANCY.AMEND |
| | THE PLANS ACCORDINGLY. |
| | |
| | 6) FBC 11-4.1.5ACCESSIBLE TOILETS AND |
| | BEDROOMS.THE EXTENT OF REQUIRED |
| | PROVISIONS WILL BE DEPENDENT UPON THE |
| | RESPONSE TO COMMENT 4 ABOVE. |
| | |
| | 7) FBC 3401.7.1ADDITIONS TO EXISTING |
| | BUILDINGS.FROM THE EXISTING AND NEW |
| | FLOOR AREAS NOW GIVEN ON SHEET A2, THE |
| | AREA OF THE ADDITION EXCEEDS 25% OF THE |
| | AREA OF THE EXISTING BUILDING.IF THE |
| | EXISTING BUILDING AND THE ADDITION ARE |
| | NOT SEPARATED BY A 4-HOUR FIRE WALL BOTH |
| | THE EXISTING BUILDING AND THE ADDITION |
| | SHALL BE MADE TO COMPLY WITH ALL |
| | REQUIREMENTS OF THE CODE FOR A BUILDING |
| | OF AREA EQUAL TO THE COMBINED AREA OF |
| | THE ADDITION AND THE EXISTING BUILDING. |
| | SUBMIT FURTHER PLANS, INCLUDING THE |
| | EXISTING BUILDING, TO DEMONSTRATE |
| | COMPLIANCE. |
| | |
| | 8) SHEET A3, GENERAL NOTES. THIS COMMENT |
| | HAS NOT BEEN PROPERLY ADDRESSED.ON THE |
| | PREVIOUSLY SUBMITTED PLAN SET, THE FIRST |
| | LINE OF THE FIRST NOTE HAD BEEN |
| | CORRECTED, BY HAND, TO READ FLORIDA |
| | BUILDING CODE INSTEAD OF STANDARD |
| | BUILDING CODE.THIS CORRECTION HAS NOT |
| | BEEN CARRIED OUT ON THE REVISED PLANS. |
| | THE SIXTH NOTE STILL REFERS TO STANDARD |
| | BUILDING CODE. AMEND ALL SUCH REFERENCES |
| | TO FLORIDA BUILDING CODE 2001. |
| | |
| | 9) SHEET A3, GENERAL STRUCTURAL NOTES. |
| | THIS COMMENT HAS NOT BEEN ADDRESSED. |
| | AMEND NOTE 1 TO REFERENCE FLORIDA |
| | BUILDING CODE AND THE CITY OF WEST PALM |
| | BEACH INSTEAD OF STANDARD BUILDING CODE |
| | AND PALM BEACH COUNTY. |
| | |
| | 10) SHEET A3, TRUSS CONNECTOR/ANCHOR |
| | SCHEDULE AND NOTES. THIS COMMENT HAS NOT |
| | BEEN PROPERLY ADDRESSED. THE SCHEDULE IS |
| | NOW LEGIBLE BUT REFERS TO 'SEMCO' WHO NO |
| | LONGER SUPPLY TRUSS CONNECTORS/ANCHORS. |
| | SPECIFY CURRENT ANCHORS.THE SCHEDULE |
| | NOTES STILL REFER TO ASCE 7-88 AND A |
| | BASIC WIND SPEED OF 110 MPH.AMEND THIS |
| | TO ASCE 7-98 AND 140 MPH.REVIEW THE |
| | SUBMITTED PLAN SETS AND AMEND ALL OTHER |
| | REFERENCES THAT INCORRECTLY CALL UP |
| | SOUTHERN BUILDING CODE, STANDARD |
| | BUILDING CODE, 110 MPH WIND SPEED AND |
| | ASCE 7-88, INCLUDING THE OCCURANCE IN |
| | THE LOAD SCHEDULE ON SHEET A3 WHICH |
| | STILL HAS NOT BEEN CORRECTED.THE ONLY |
| | CORRECTION THAT HAS BEEN MADE IS THE |
| | BASIC WIND SPEED ON THE LOAD SCHEDULE. |
| | |
| | 12) FBC 11-4.1.2(1)EXTERIOR RAMPS TO |
| | THE NEW HALL AND THE NEW PATIO HALL. |
| | THE PLANS HAVE BEEN REVISED TO EXTEND |
| | THESE RAMPS TO ACHIEVE COMPLIANT |
| | GRADIENTS.AS A RESULT OF THE EXTENSION |
| | THE SIDEWALKS LEADING TO THE BASE OF THE |
| | RAMPS WILL REQUIRE ADJUSTMENT TO ALLOW |
| | UNRESTRICTED WHEELCHAIR ACCESS TO EACH |
| | RAMP. |
| | |
| | 14) SHUTTER PRODUCT APPROVAL DOCUMENTS. |
| | THE DRAWING SUBMITTED WITH EASTERN METAL |
| | SUPPLY INC. SBCCI TESTING & EVALUATION |
| | REPORT NO. 2211 ARE NOT THE SAME SHEETS |
| | REFERENCED IN 6.1 SUBSTANTIATING DATA ON |
| | PAGE 7 OF 8. SUBMIT DRAWING SHEETS WHICH |
| | CORRESPOND TO THE TEST REPORT. |
| | |
| | THE FOLLOWING ARE NEW COMMENTS ARISING |
| | FROM REVIEW OF THE REVISED PLANS: |
| | |
| | 17) FBC* 104.2.1.3TWO VERSIONS OF |
| | SHEET A1 WERE SUBMITTED WITH DIFFERENT |
| | INFORMATION ON EACH.RE-NUMBER THE |
| | MOST RECENT (WITH THE LANDSCAPING) TO |
| | DIFFERENTIATE IT FROM THE VERSION |
| | PREVIOUSLY SUBMITTED. |
| | |
| | 18) FBC* 104.2.1.3 SHEET A2 AND SHEET A7 |
| | (DOOR SCHEDULE) HAVE PENCIL NOTES ADDED. |
| | THE USE OF PENCIL IS NOT APPROPRIATE ON |
| | PLANS FOR PERMITTING PURPOSES.AMEND |
| | THE PLANS IN INK. |
| | |
| | 19) SHEET D1, CONCRETE BEAM SCHEDULE. |
| | THE PREVIOUSLY SUBMITTED PLAN SET |
| | INCLUDED HANDWRITTEN NOTES FOR BEAM TYPE |
| | RB-3. THESE NOTES HAVE BEEN OMITTED FROM |
| | THE REVISED PLAN SET. |
| | |
| | 20) SHEET S1, FOUNDATION PLAN.THE |
| | PREVIOUSLY SUBMITTED PLAN SET INCLUDED |
| | HANDWRITTEN NOTES SPECIFYING VERTICAL |
| | REBAR DOWELS ON EACH SIDE OF THE DOOR |
| | AND WINDOW OPENINGS.THESE NOTES HAVE |
| | BEEN OMITTED FROM THE REVISED PLAN SET. |
| | |
| | 21) IF NEW PLAN SHEETS ARE REQUIRED, IN |
| | ORDER TO ADDRESS THE ABOVE COMMENTS, THE |
| | OLD SHEETS SHALL BE REMOVED AND THE NEW |
| | SHEETS INSERTED.ONE COPY OF EACH OLD |
| | SHEET SHALL BE INCLUDED WITH THE |
| | RESUBMITTAL FOR COMPARISON OF REVISIONS. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | IF YOU HAVE ANY QUESTIONS PLEASE CALL: |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |