Plan Review Notes
Plan Review Notes For Permit 02101723
Permit Number 02101723
Review Stop E
Sequence Number 1
Notes
Date Text
2002-10-28 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} IT IS UNCLEAR IF THE SERVICE IS TO BE
 REPLACED, IF IT IS PLEASE SHOW THE GEC.
 SYSTEM.
  
 3} PLEASE SUBMIT A DRAWING OF THE
 KITCHEN SHOWING THE LOCATIONS OF ALL
 DEVICES BEING ADDED.ALSO NOTE THE RANGE
 RECEPTACLE MUST COMPLY WITH 250-140.
  
 4} PLEASE NOTE KITCHEN COUNTER-
 -SPACE RECEPT SPACING SHALL MEET ART;
 210-52C 1,2,3,4,AND 5.AND MUST BE GFI
 PER 210-8(A)(7)CWPB AMMENDMENTS.
  
 5} NOTE THAT THE PANEL BEING REPLACED
 MUST COMPLY WITH 230-70(A)CWPB
 AMMENDMENTS(NOT MORE THAN 8' OF
 CONDUCTORS IN THE BUILDING,ETC.).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392