| 2002-11-21 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION AND RESUBMIT FOR REVIEW. | | | | | | 1} THE PANEL SCHEDULE AND LOAD | | | CALCULATION ON THE PLAN IS NOT | | | CLEAR.PLEASE PROVIDE A PANEL SCHEDULE | | | FOR ALL PANELS,WITH LOAD CALCULATIONS | | | FOR SAME. | | | | | | 2} INDICATE THE SIZE OF THE EXISTING | | | SERVICE,AND THE SIZE OF THE PANEL(S) | | | BEING ADDED,ALSO THE LOCATION. | | | | | | 3} NOTE THE SMALL APPLIANCE CIRCUITS PER | | | 220-16@ 1500 VA.THERE ARE 3 LISTED @ | | | 3000 VA. | | | | | | 4} PLEASE LIST THE REQ'D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG. | | | | | | 5} PLEASE LIST THE REQ'D ARC | | | FAULT PROTECTED CIRCUITS ON PANEL | | | SCHEDULE PER 210-12. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT.8392 |
|