Plan Review Notes
Plan Review Notes For Permit 02101678
Permit Number 02101678
Review Stop E
Sequence Number 1
Notes
Date Text
2002-11-21 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION AND RESUBMIT FOR REVIEW.
  
 1} THE PANEL SCHEDULE AND LOAD
 CALCULATION ON THE PLAN IS NOT
 CLEAR.PLEASE PROVIDE A PANEL SCHEDULE
 FOR ALL PANELS,WITH LOAD CALCULATIONS
 FOR SAME.
  
 2} INDICATE THE SIZE OF THE EXISTING
 SERVICE,AND THE SIZE OF THE PANEL(S)
 BEING ADDED,ALSO THE LOCATION.
  
 3} NOTE THE SMALL APPLIANCE CIRCUITS PER
 220-16@ 1500 VA.THERE ARE 3 LISTED @
 3000 VA.
  
 4} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 5} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE PER 210-12.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT.8392