Plan Review Notes
Plan Review Notes For Permit 02101660
Permit Number 02101660
Review Stop R
Sequence Number 2
Notes
Date Text
2003-03-13 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) THE PLANS HAVE BEEN WHITED OUT AND
 CHANGES HAVE BEEN RED LINED. THE
 ARCHITECT IS REQUIRED TO INITIAL AND
 DATE ALL THE CHANGES THAT HAVE BEEN
 WRITTEN ON THE PLANS.
  
 4) THE WRONG FORM WAS SUBMITTED FOR THE
 ENERGY CALCULATIONS. THE CORRECT FORM
 FOR THE RESIDENTIAL WHOLE BUILDING
 METHOD IS 600A. NOTE: THE FORM IS
 REQUIRED TO BE SIGNED BY THE OWNER/AGENT
  
 5) INDICATE THE STAIR RISER HEIGHT ON
 THE PLANS. NOTE: THE SUM OF TWO RISERS
 AND A TREAD EXCLUSIVE OF THE NOSING MUST
 BE BETWEEN 24 AND 25 INCHES.FBC 1007.3
  
 6) THE MINIMUM HEIGHT OF A GUARDRAIL ON
 THE OPEN SIDE OF STAIRS IS 36" PER FBC
 1015 AND 1026.5.1. THE INTERMEDIATE
 RAILS ARE REQUIRED TO REJECT THE PASSAGE
 OF A 4" SPHERE PER FBC 1015.3. PLEASE
 REVISE THE STAIR DETAIL ON A2.
  
 7) CIRCULAR STAIRS ARE REQUIRED TO HAVE
 A MINIMUM TREAD DEPTH OF 9" WITH 1" OF
 NOSING PER FBC 1007.8.3. DRAWINGS APPEAR
 TO SHOW TREADS NARROWER THAN THIS AT THE
 SMALLER RADIUS OF THE STAIR. PLEASE
 INDICATE THIS ON THE PLANS.
  
 8) FBC 2305.2.2 REQUIRES THE FLOOR/
 CEILING ASSEMBLY TO BE DIVIDED INTO
 AREAS OF NO MORE THAN 500 SQ FT BY
 DRAFTSTOPPING. INDICATE ON THE PLANS
 THE LOCATIONS OF THESE DIVISIONS AND THE
 MATERIAL THAT WILL BE USED FOR DRAFTSTOP
  
 9) SHEET A1 SHOWS THE DRYER BEING VENTED
 INTO THE GARAGE. THE FBC MECHANICAL CODE
 504.4 REQUIRES THE DRYER VENT TO
 TERMINATE ON THE OUTSIDE OF THE BUILDING
  
 10) THE WALL SECTION AT THE STUDY IS
 MISMARKED. THE SECTION IS SHOWN ON SHEET
 A4. THE SECTION ON A4 IS ALSO MISMARKED
 AS A3. PLEASE CORRECT.
  
 11) PROVIDE BUCK DETAILS FOR THE
 EXTERIOR WINDOWS, DOORS AND OVERHEAD
 GARAGE DOORS.
  
 12) PROVIDE (2) PRODUCT APPROVALS, KEY
 PLANS AND INSTALLATION SCHEDULES
 INDICATING THE SPECIFIC TYPES OF ANCHORS
 TO BE USED FOR STORM PANELS. IF NOT
 PROVIDED AT THIS TIME A SEPARATE PERMIT
 AND ADDITIONAL FEES WILL BE REQUIRED.
  
 13) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - STRUCTURAL MULLIONS
 - 16' WIDE GARAGE DOOR
 - 9' WIDE GARAGE DOOR (THE ONE THAT WAS
 SUBMITTED IS ILLEGIBLE)
 - THE SINGLE OUTSWING/INSWING DOOR IS
 MISSING THE 6 PAGES OF DRAWINGS
 - THE INFORMATION SUBMITTED FOR THE
 NORANDEX PRODUCTS (HORIZONTAL SLIDING
 WINDOWS, FIXED WINDOWS AND SLIDING GLASS
 DOOR ARE NOT ACCEPTABLE WITHOUT SITE
 SPECIFIC ENGINEERING. SEE ATTACHED
 PRODUCT APPROVAL FORM. IT MUST BE FILLED
 OUT AND SIGNED, SEALED AND DATED BY THE
 ENGINEER FOR THE PRODUCT AND SIGNED,
 SEALED AND DATED BY THE DESIGNER OF
 RECORD FOR THE STRUCTURE PER BUILDING
 OFFICIAL. SEE FBC 103.7 ALTERNATE
 MATERIALS AND METHODS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202