| 2003-03-13 00:00:00 | BUILDING DENIED |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3) THE PLANS HAVE BEEN WHITED OUT AND |
| | CHANGES HAVE BEEN RED LINED. THE |
| | ARCHITECT IS REQUIRED TO INITIAL AND |
| | DATE ALL THE CHANGES THAT HAVE BEEN |
| | WRITTEN ON THE PLANS. |
| | |
| | 4) THE WRONG FORM WAS SUBMITTED FOR THE |
| | ENERGY CALCULATIONS. THE CORRECT FORM |
| | FOR THE RESIDENTIAL WHOLE BUILDING |
| | METHOD IS 600A. NOTE: THE FORM IS |
| | REQUIRED TO BE SIGNED BY THE OWNER/AGENT |
| | |
| | 5) INDICATE THE STAIR RISER HEIGHT ON |
| | THE PLANS. NOTE: THE SUM OF TWO RISERS |
| | AND A TREAD EXCLUSIVE OF THE NOSING MUST |
| | BE BETWEEN 24 AND 25 INCHES.FBC 1007.3 |
| | |
| | 6) THE MINIMUM HEIGHT OF A GUARDRAIL ON |
| | THE OPEN SIDE OF STAIRS IS 36" PER FBC |
| | 1015 AND 1026.5.1. THE INTERMEDIATE |
| | RAILS ARE REQUIRED TO REJECT THE PASSAGE |
| | OF A 4" SPHERE PER FBC 1015.3. PLEASE |
| | REVISE THE STAIR DETAIL ON A2. |
| | |
| | 7) CIRCULAR STAIRS ARE REQUIRED TO HAVE |
| | A MINIMUM TREAD DEPTH OF 9" WITH 1" OF |
| | NOSING PER FBC 1007.8.3. DRAWINGS APPEAR |
| | TO SHOW TREADS NARROWER THAN THIS AT THE |
| | SMALLER RADIUS OF THE STAIR. PLEASE |
| | INDICATE THIS ON THE PLANS. |
| | |
| | 8) FBC 2305.2.2 REQUIRES THE FLOOR/ |
| | CEILING ASSEMBLY TO BE DIVIDED INTO |
| | AREAS OF NO MORE THAN 500 SQ FT BY |
| | DRAFTSTOPPING. INDICATE ON THE PLANS |
| | THE LOCATIONS OF THESE DIVISIONS AND THE |
| | MATERIAL THAT WILL BE USED FOR DRAFTSTOP |
| | |
| | 9) SHEET A1 SHOWS THE DRYER BEING VENTED |
| | INTO THE GARAGE. THE FBC MECHANICAL CODE |
| | 504.4 REQUIRES THE DRYER VENT TO |
| | TERMINATE ON THE OUTSIDE OF THE BUILDING |
| | |
| | 10) THE WALL SECTION AT THE STUDY IS |
| | MISMARKED. THE SECTION IS SHOWN ON SHEET |
| | A4. THE SECTION ON A4 IS ALSO MISMARKED |
| | AS A3. PLEASE CORRECT. |
| | |
| | 11) PROVIDE BUCK DETAILS FOR THE |
| | EXTERIOR WINDOWS, DOORS AND OVERHEAD |
| | GARAGE DOORS. |
| | |
| | 12) PROVIDE (2) PRODUCT APPROVALS, KEY |
| | PLANS AND INSTALLATION SCHEDULES |
| | INDICATING THE SPECIFIC TYPES OF ANCHORS |
| | TO BE USED FOR STORM PANELS. IF NOT |
| | PROVIDED AT THIS TIME A SEPARATE PERMIT |
| | AND ADDITIONAL FEES WILL BE REQUIRED. |
| | |
| | 13) PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - STRUCTURAL MULLIONS |
| | - 16' WIDE GARAGE DOOR |
| | - 9' WIDE GARAGE DOOR (THE ONE THAT WAS |
| | SUBMITTED IS ILLEGIBLE) |
| | - THE SINGLE OUTSWING/INSWING DOOR IS |
| | MISSING THE 6 PAGES OF DRAWINGS |
| | - THE INFORMATION SUBMITTED FOR THE |
| | NORANDEX PRODUCTS (HORIZONTAL SLIDING |
| | WINDOWS, FIXED WINDOWS AND SLIDING GLASS |
| | DOOR ARE NOT ACCEPTABLE WITHOUT SITE |
| | SPECIFIC ENGINEERING. SEE ATTACHED |
| | PRODUCT APPROVAL FORM. IT MUST BE FILLED |
| | OUT AND SIGNED, SEALED AND DATED BY THE |
| | ENGINEER FOR THE PRODUCT AND SIGNED, |
| | SEALED AND DATED BY THE DESIGNER OF |
| | RECORD FOR THE STRUCTURE PER BUILDING |
| | OFFICIAL. SEE FBC 103.7 ALTERNATE |
| | MATERIALS AND METHODS. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |