| 2003-03-10 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE MAKE NECESSARY CHANGES TO SHOW | | | CODE COMPLIANCE ON PLANS. | | | | | | 1} PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG.ON PANEL SCHEDULE | | | | | | 2} PLEASE LIST THE REQ`D ARC | | | FAULT PROTECTED CIRCUITS ON PANEL | | | SCHEDULE,PER 210-12. | | | | | | 3} GROUNDING ELECTRODE SYSTEM TO INCLUDE | | | 250-50(C). | | | | | | 4} THE EQUIPMENT GROUND FROM THE METER | | | TO THE FIRST MEANS OF DISCONNECT | | | CREATES A PARALLEL GROUND PATH WITH THE | | | NEUTRAL AND MUST BE REMOVED. | | | | | | 5} THE OCP FOR THE 12KW. RANGE IS | | | INCORRECT. | | | | | | 6} PLEASE SHOW THE RECEPTACLES SERVING | | | THE KICHEN COUNTERTOPS IN COMPLIANCE | | | WITH 210-8(A)(6) AND 210-52(C) | | | | | | IF THERE ARE ANY QUESTION PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT.8392 |
|