2003-03-10 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE NECESSARY CHANGES TO SHOW
 CODE COMPLIANCE ON PLANS.
  
 1} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.ON PANEL SCHEDULE
  
 2} PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE,PER 210-12.
  
 3} GROUNDING ELECTRODE SYSTEM TO INCLUDE
 250-50(C).
  
 4} THE EQUIPMENT GROUND FROM THE METER
 TO THE FIRST MEANS OF DISCONNECT
 CREATES A PARALLEL GROUND PATH WITH THE
 NEUTRAL AND MUST BE REMOVED.
  
 5} THE OCP FOR THE 12KW. RANGE IS
 INCORRECT.
  
 6} PLEASE SHOW THE RECEPTACLES SERVING
 THE KICHEN COUNTERTOPS IN COMPLIANCE
 WITH 210-8(A)(6) AND 210-52(C)
  
 IF THERE ARE ANY QUESTION PLEASE CALL.
  