Plan Review Notes
Plan Review Notes For Permit 02101660
Permit Number 02101660
Review Stop R
Sequence Number 1
Notes
Date Text
2002-12-02 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
 INDICATE THE INTERNAL PRESSURE
 COEFFICIENT, WHICH IS + OR - 0.18 FOR AN
 ENCLOSED STRUCTURE. PLEASE CORRECT THE
 IMPORTANCE FACTOR, WHICH SHOULD BE 1.00.
  
 4) PLEASE REVISE GENERAL NOTES 3,8 & 10
 ON C1 TO REFERENCE THE FLORIDA BUILDING
 CODE AND 140 MPH WIND ZONE.
  
 5) PROVIDE ENERGY CALCULATIONS, REQUIRED
 BY CHAPTER 13 OF THE FBC.
  
 6) PROVIDE FLOOR AND ROOF FRAMING PLANS.
 PROVIDE A CONNECTOR SCHEDULE AND
 INDICATE THE LOADS TO BE RESISTED.
  
 7) PROVIDE DETAILS OF THE STAIRS, HAND-
 RAILS AND GUARDRAILS WHICH COMPLY WITH
 FBC SECTIONS 1007, 1007.5 AND 1015.
  
 8) PROVIDE DETAILS FOR THE GUARDRAILS AT
 THE EXTERIOR BALCONY WHICH SHOW
 COMPLIANCE WITH FBC SECTIONS 1015 AND
 1608.2.2. INDICATE HEIGHT, INTERMEDIATE
 RAIL SPACING, MATERIAL, CONNECTIONS TO
 STRUCTURE, ETC.
  
 9) INDICATE THE LOCATIONS AND MATERIALS
 THAT WILL BE USED FOR DRAFTSTOPPING THE
 FLOOR/CEILING ASSEMBLY INTO 500 SQFT
 AREAS AS REQUIRED BY FBC 2305.2.2.
  
 10) PROVIDE CONSTRUCTION DETAILS FOR THE
 SECOND FLOOR EXTERIOR BALCONY.
  
 11)FL BLD CODE 2309.6 ATTIC ACCESS, PRO-
 VIDE ATTIC ACCESS 20"X36". REQUIRED FOR
 ALL ATTIC SPACES WITH 24" CLEAR HEIGHT.
  
 12) SPECIFY THE SIZE AND SPACING OF THE
 ATTIC VENTS ON A4. THE RATIO OF NET FREE
 VENTILATING AREA TO THE AREA OF THE
 CEILING SHALL BE MINIMUM OF 1/150. SEE
 FBC 2309.7.
  
 13) CLARIFY THE FOOTINGS FOR THE 16"
 DIAMETER CONCRETE FILLED BLOCK COLUMNS
 AT THE FRONT PORCH.
  
 14) SPECIFY THE CONNECTION OF THE SECOND
 FLOOR EXTERIOR WOOD FRAME BEARING WALL
 TO THE WOOD GIRDER TRUSS. SEE A2.
  
 15) SPECIFY THE BOLT TYPE, LENGTH AND
 EMBEDDMENT FOR THE HD2A/ADS2 CONNECTORS
 INDICATED IN DETAIL 8/A8.
  
 16) SPECIFY THE COLUMN SUPPORTING THE
 GIRDER TRUSS AT THE LIVING ROOM AND THE
 BUILT-UP WOOD COLUMNS SHOWN ON A3.
 SPECIFY THE CONNECTORS AT THE TOPS AND
 BOTTOMS OF THESE COLUMNS. PLEASE CLARIFY
 WHICH ONE OF THE TWO COLUMNS SHOWN IN
 DETAIL 8/A8 IS TO BE USED AT EACH
 LOCATION.
  
 17) PLEASE CLARIFY THE SECTION AT THE
 STUDY WALL ON A3 THAT IS MARKED 4/A3.
 THERE IS NO SECTION OR DETAIL 4 ON SHEET
 A3.
  
 18) THE CITY OF WPB AMENDMENTS TO THE
 FBC 2111.1.9 REQUIRES A 1-1/2" RECESS IN
 MONOLITHIC FOUNDATIONS FOR A WATERSTOP.
 PLEASE REVISE SECTIONS ON A4.
  
 19) THE FBC SECTION 1909.3 REQUIRES THAT
 WELDED WIRE MESH USED IN THE SLAB BE
 SUPPORTED ON APPROVED MATERIALS AT
 SPACINGS NOT TO EXCEED 3 FEET.
  
 20)FBC 905.2.2 REQUIRES A SMOKE DETECTOR
 ON THE FIRST FLOOR IN CLOSE PROXIMITY TO
 THE STAIRWAY LEADING TO THE FLOOR ABOVE.
  
 21)INDICATE FIREBLOCKING WHERE CONCEALED
 SPACES OF WALLS AND FLOORS OR CEILINGS
 MEET. IT IS ALSO REQUIRED AT CONCEALED
 SPCACES BETWEEN STAIR STRINGERS AT THE
 TOP AND BOTTOM OF RUNS. SEE FBC 2305.1.
  
 22) REVISE THE CONCRETE TILE NAILING
 INFORMATION ON A4 TO REFERENCE THE FBC.
  
 23) SPECIFY THE SPECIAL ROOF SHEATHING
 NAILING REQUIREMENTS PER THE CITY OF WPB
 AMENDMENTS TO THE FBC TABLE 2306.1.
  
 24) SPECIFY THE TYPE, DIAMETER AND
 EMBEDMENT DEPTH FOR THE BOLTS USED TO
 ATTACH THE LEDGERS SUPPORTING THE FLOOR
 TRUSSES SHOWN IN THE SECTION ON A4.
  
 25) ALL THE IDENTIFING MARKS FOR THE
 SECTIONS AND THE SECTIONS GIVEN ON A4
 ARE INCORRECTLY LABELED AS A3. PLEASE
 CORRECT.
  
 26) PROVIDE BUCK ATTACHMENT DETAILS FOR
 WINDOWS, DOORS AND OVERHEAD GARAGE DOORS
  
 27) SAFETY GLASS IS REQUIRED WITHIN 3
 FEET OF A TUB OR SHOWER PER FBC 2405.2.
 PLEASE INDICATE TEMPERED GLASS AT THESE
 WINDOWS ON THE PLANS.
  
 28)PROVIDE (2) PRODUCT APPROVALS, KEY
 PLANS AND INSTALLATION SCHEDULES
 INDICATING THE SPECIFIC TYPES OF ANCHORS
 TO BE USED FOR STORM PANELS.
  
 29) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - HORIZONTAL SLIDING WINDOWS
 - HORIZONTAL AND VERTICAL STRUCTURAL
 MULLIONS
 - FIXED GLASS WINDOWS (RECTANGULAR AND
 ARCHED)
 - 4 PANEL SLIDING GLASS DOOR
 - OVERHEAD GARAGE DOORS
 - WOOD OR METAL OUTSWING DOOR AT GARAGE
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202