| 2002-11-20 00:00:00 | UNSAT |
| | ~~~~~ |
| | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| | PLEASE PROVIDE THE FOLLOWING |
| | INFORMATION,MAKE ANY NECESSARYCHANGES |
| | TO PLANS,AND RESUBMIT FOR REVIEW. |
| | |
| | 1} PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 2} PLEASE LIST THE REQ'D BATH(S) |
| | CIRCUIT(S). PER 210-11-C-3 |
| | MUST BE 20A AND #12AWG,ON THE PANEL |
| | SCHEDULE. |
| | |
| | 3} PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CIRCUITS ON PANEL |
| | SCHEDULE PER 210-12. |
| | |
| | 4} SHOW METER MAIN LOCATION ON PLANS. |
| | |
| | 5} GEC SYSTEM TO INCLUDE |
| | 250-50(C).PLEASE INDICATE SAME ON RISER |
| | DIAGRAM. |
| | |
| | 6} THE CONDUIT FROM THE MAIN DISCONNECT |
| | TO THE PANEL MUST COMPLY WITH 250-110(EQ |
| | GND.). |
| | |
| | 7} THE #10 CONDUCTOR FOR THE RANGE IS |
| | INCORRECT FOR THE LOAD SERVED AND THE |
| | OCP. |
| | |
| | 8} A WP. GFI IS REQUIRED IN THE FRONT OF |
| | THE RESIDENCE PER 210-52(E). |
| | |
| | 9} IF THE RECEPTACLE SYMBOLS AT EACH |
| | COMPRESSER LOCATION ARE MEANT TO |
| | REPRESENT DISCONNECTS,NOTE THAT THEY |
| | MUST COMPLY WITH 110-26. |
| | |
| | 10} PLEASE NOTE THAT THE RECEPTACLES |
| | SERVING KITCHEN COUNTERTOPS MUST COMPLY |
| | WITH 210-8(A)(6) AND 210-52(C). |
| | |
| | 11} THE BATH RECEPTACLE LOCATION MUST |
| | COMPLY WITH 210-52(D).NOTE BATHS OFF |
| | BR'S 2 & 5. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/659-8096 EXT. 8392. |