Plan Review Notes
Plan Review Notes For Permit 02101660
Permit Number 02101660
Review Stop E
Sequence Number 1
Notes
Date Text
2002-11-20 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE ANY NECESSARYCHANGES
 TO PLANS,AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG,ON THE PANEL
 SCHEDULE.
  
 3} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE PER 210-12.
  
 4} SHOW METER MAIN LOCATION ON PLANS.
  
 5} GEC SYSTEM TO INCLUDE
 250-50(C).PLEASE INDICATE SAME ON RISER
 DIAGRAM.
  
 6} THE CONDUIT FROM THE MAIN DISCONNECT
 TO THE PANEL MUST COMPLY WITH 250-110(EQ
 GND.).
  
 7} THE #10 CONDUCTOR FOR THE RANGE IS
 INCORRECT FOR THE LOAD SERVED AND THE
 OCP.
  
 8} A WP. GFI IS REQUIRED IN THE FRONT OF
 THE RESIDENCE PER 210-52(E).
  
 9} IF THE RECEPTACLE SYMBOLS AT EACH
 COMPRESSER LOCATION ARE MEANT TO
 REPRESENT DISCONNECTS,NOTE THAT THEY
 MUST COMPLY WITH 110-26.
  
 10} PLEASE NOTE THAT THE RECEPTACLES
 SERVING KITCHEN COUNTERTOPS MUST COMPLY
 WITH 210-8(A)(6) AND 210-52(C).
  
 11} THE BATH RECEPTACLE LOCATION MUST
 COMPLY WITH 210-52(D).NOTE BATHS OFF
 BR'S 2 & 5.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392.