Plan Review Notes
Plan Review Notes For Permit 02101626
Permit Number 02101626
Review Stop M
Sequence Number 1
Notes
Date Text
2002-11-20 00:00:00PROVISO:
  
 PLEASE NOTE AHU IN GARAGE SHALL BE
 PROTECTED FROM DAMAGE AS PER 2001
 FBC(M) 303.4.
  
 SMOKE DETECTORS SHALL BE INSTALLED
 SUPPLY SYSTEMS WITH A DESIGN CAPACITY
 GREATER THAN 2,000 CFM, IN THE SUPPLY
 AIR DUCT. 2001 FBC(M) 606.2.1OR
 UPON ACTIVATION, THE SMOKE DETECTORS
 SHALL SHUTDOWN THE AIR DISTRIBUTION
 SYSTEM. 2001 FBC(M) 606.4
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.