| 2002-11-27 00:00:00 | ***************** UNSAT ************* |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATING FOR |
| | NEW MAIN AND PANEL. ALL MUST BE RATED |
| | FOR THE AVAILABLE FAULT CURRENT. |
| | |
| | 2)NOTE: PLEASE LIST THE REQ`D BATH |
| | CIRCUIT(S) PER 210-52D AND 210-11-C-3 |
| | |
| | 3)NOTE: PLEASE NOTE AHU/HEAT LOAD WAS |
| | DEDUCTED IN THE REST OF THE LOAD |
| | CALCS AND NEEDS TO BE FIGURED FROM |
| | GENERAL LIGHTING AND RECEPT LOADS. |
| | 220 NEC |
| | |
| | 4)NOTE: PLEASE NOTE, MISSING EQUIPMENT |
| | GROUNDING CONDUCTOR BETWEEN MAIN AND |
| | PANEL. 250-24 AND SIZE PER 250-122 |
| | |
| | 5)NOTE: PLEASE NOTE, MISSING RECEPT |
| | FOR KITCHEN COUNTER PENINSULAR.210-52C-3 |
| | GFI PER 210-8-A-6 |
| | |
| | 6)NOTE: PLEASE LIST THE REQ`D ARC FAULT |
| | PROTECTED CIRCUITS PER 210-12 FOR NEW |
| | BEDROOMS. |
| | |
| | 7)NOTE: PLEASE NOTE SD NEEDS TO BE A MIN |
| | OF 3' FROM BATH DOOR. NFPA-72 8-1.4.1.6 |
| | |
| | 8)NOTE: PLEASE NOTE MISSING RECPET, 2' |
| | OF WALL NEW BEDROOM. 210-52 |
| | |
| | |
| | JUST A NOTE, IF THERE ARE GOING TO BE |
| | NEW LOW VOLTAGE, (PHONE,CATV,SOUND) |
| | PLEASE SHOW ON PLANS IN ORDER TO BE |
| | PERMITTED UNDER THE WORK.IF NOT A |
| | SEPARATE PERMIT WILL BE REQ`D AND SEPAR- |
| | ATE LAYOUT SUBMITTED. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |