Plan Review Notes
Plan Review Notes For Permit 02101626
Permit Number 02101626
Review Stop E
Sequence Number 1
Notes
Date Text
2002-11-27 00:00:00***************** UNSAT *************
  
 1)NOTE: PLEASE SUBMIT AIC RATING FOR
 NEW MAIN AND PANEL. ALL MUST BE RATED
 FOR THE AVAILABLE FAULT CURRENT.
  
 2)NOTE: PLEASE LIST THE REQ`D BATH
 CIRCUIT(S) PER 210-52D AND 210-11-C-3
  
 3)NOTE: PLEASE NOTE AHU/HEAT LOAD WAS
 DEDUCTED IN THE REST OF THE LOAD
 CALCS AND NEEDS TO BE FIGURED FROM
 GENERAL LIGHTING AND RECEPT LOADS.
 220 NEC
  
 4)NOTE: PLEASE NOTE, MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN MAIN AND
 PANEL. 250-24 AND SIZE PER 250-122
  
 5)NOTE: PLEASE NOTE, MISSING RECEPT
 FOR KITCHEN COUNTER PENINSULAR.210-52C-3
 GFI PER 210-8-A-6
  
 6)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTED CIRCUITS PER 210-12 FOR NEW
 BEDROOMS.
  
 7)NOTE: PLEASE NOTE SD NEEDS TO BE A MIN
 OF 3' FROM BATH DOOR. NFPA-72 8-1.4.1.6
  
 8)NOTE: PLEASE NOTE MISSING RECPET, 2'
 OF WALL NEW BEDROOM. 210-52
  
  
 JUST A NOTE, IF THERE ARE GOING TO BE
 NEW LOW VOLTAGE, (PHONE,CATV,SOUND)
 PLEASE SHOW ON PLANS IN ORDER TO BE
 PERMITTED UNDER THE WORK.IF NOT A
 SEPARATE PERMIT WILL BE REQ`D AND SEPAR-
 ATE LAYOUT SUBMITTED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372