| 2003-02-12 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | 1) FBC* 104.2.1.2IT IS EVIDENT FROM |
| | THE ARCHITECTURAL PLANS THAT THE SCOPE |
| | OF WORK HAS CHANGED TO EXCLUDE THE |
| | RELOCATED MED-GAS STORAGE ENCLOSURE AND |
| | INCLUDE A BIO-HAZARD STORE AND DUMPSTER |
| | ENCLOSURE.THE REVISED SHEET A1.03 |
| | REFERS TO THE CIVIL AND STRUCTURAL PLANS |
| | FOR STEEL BOLLARD, CMU WALL, CONCRETE |
| | BOND BEAM, CONCRETE SLAB AND CONCRETE |
| | FOOTING DETAILS.THE CIVIL AND |
| | STRUCTURAL PLANS HAVE NOT BEEN REVISED |
| | TO INCLUDE THE REQUIRED DETAILS |
| | |
| | 2) MECHANICAL SHEET M3.01, DETAIL 12 AND |
| | 13 (NOTE 2).WIND LOAD ON ROOF-MOUNTED |
| | MECHANICAL EQUIPMENT.THE FLORIDA |
| | BUILDING CODE IS NOT 2002, AND THE |
| | SECTION QUOTED DOES NOT EXIST.THE |
| | CORRECT REFERENCE IS FLORIDA BUILDING |
| | CODE 2001, SECTION 1606.1.AMEND THE |
| | NOTES. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | IF YOU HAVE ANY QUESTIONS PLEASE CALL: |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |