| Plan Review Notes For Permit 02101618 |
| Permit Number |
02101618 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-11-13 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 FUEL GAS | | | FBC-2001 CHAPTER 11 | | | | | | 1) SHT P1.01 CONDENSATE SHALL DRAIN TO | | | THE EXTERIOR OF THE BLDG SEPARATELY. | | | CONDENSATE SHALL NOT TIE INTO THE RAIN | | | CONDUCTORS INSIDE THE BLDG AND SHALL NOT | | | DRAIN INTO FLOOR DRAINS FOR THE SANITARY | | | SYSTEM. CONDENSATE SHALL TIE INTO STORM, | | | CATCHBASIN OR DRYWELL OUTSIDE OF THE | | | BUILDING WITH A RELIEF VENT IN THE LINE | | | AS IT EXITS THE BLDG. SHT P2.01 SAME | | | NOTES APPLY. | | | 2) SEPARATE GAS PERMIT REQUIRED FOR ANY | | | NATURAL GAS WORK BEING DONE INSIDE BLDG. | | | | | | ----MED GAS SEPARATE REVIEW----- | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|