Plan Review Notes
Plan Review Notes For Permit 02101618
Permit Number 02101618
Review Stop B
Sequence Number 1
Notes
Date Text
2002-11-06 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.FOR INFORMATION.
  
 2) IMPACT FEE MUST BE PAID TO PALM BEACH
 COUNTY, THE PLANS STAMPED BY THEM AND A
 COPY OF THE RECEIPT SUBMITTED TO THE
 CITY OF WEST PALM BEACH, DEPARTMENT OF
 CONSTRUCTION SERVICES, BEFORE A BUILDING
 PERMIT CAN BE ISSUED.FOR INFORMATION.
  
 3) FBC 1504.1SUBMIT A PRODUCT APPROVAL
 FOR THE ROOF COVERING.
  
 4) FBC 704.1.3.3FIRE RESISTANT
 SEPARATION AT THE WALL BETWEEN THE NEW
 MECH ROOM (1-143) AND BODY HOLD (1-146)
 AND TOILET (1-144) AND AT THE WALL
 BETWEEN THE MECH ROOM (1-143) AND THE
 NITROUS OXIDE ROOM SHALL BE PROVIDED IN
 ACCORDANCE WITH ANY FIRE PLAN REVIEW
 COMMENTS.THE NITROUS OXIDE ROOM WALL,
 WHICH WAS EXTERIOR WALL, IS TO BECOME AN
 INTERIOR WALL TO THE MECH ROOM.FROM
 SHEET M2.01, THE MECH ROOM APPEARS TO BE
 FOR AIR HANDLING EQUIPMENT AND DUCTS.
 FIRE RESISTANT SEPARATION MAY BE
 REQUIRED IF THE ROOM IS TO HOUSE ANY
 OTHER MECHANICAL EQUIPMENT.