| Plan Review Notes For Permit 02101617 |
| Permit Number |
02101617 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-12-10 00:00:00 | THE FIRE PROTECTION FOR THE NEW | | | STRUCTURAL BEAMS IS NOT SHOWN ON THE | | | PLANS AS WAS REQUESTED IN THE 11/05/02 | | | PLAN REVIEW COMMENTS.FBC TABLE 600 | | | REQUIRES 2 HR FIRE RESISTANT PROTECTION | | | FOR BEAMS, GIRDERS AND ARCHES SUPPORTING | | | ONE FLOOR AND FOR FLOOR CEILING | | | ASSEMBLIES. | | | | | | THE 11TH FLOOR LIFE SAFETY DIAGRAM HAS | | | NEITHER DIMENSIONS OR SCALE.IT | | | APPEARS THAT THE COMMON PATH OF TRAVEL | | | WILL EXCEED THE 75' ALLOWED BY FBC | | | 1004.1.3 AND 1004.1.2.PLEASE CLARIFY. | | | | | | PLEASE COLLATE THE PLANS INTO TWO | | | CONCISE SETS AND REMOVE ANY VOID OR | | | OBSOLETE PAGES. |
|