| Plan Review Notes For Permit 02101617 |
| Permit Number |
02101617 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-11-05 00:00:00 | SHOW THE FIRE PROTECTION FOR THE STEEL | | | BEAMS AS REQUIRED BY FBC TABLE 600 | | | (2HRS) | | | | | | SHOW A DETAIL OR SCHEDULE FOR THE | | | CONCRETE SLAB REINFORCING. | | | | | | THE STRUCTURAL SHEET DECLARES DESIGN TO | | | THE 1997 SBC.PLEASE REVISE AND ENSURE | | | COMPLIANCE WITH FBC 2001 | | | | | | PLEASE PROVIDE A LIFE SAFETY PLAN LAYOUT | | | FOR THE 11TH AND 12TH FLOORS INDICATING | | | THE EGRESS AND TENANT SEPARATIONS | | | WHERE NECESSARY.FBC 104.2. |
|