| Notes |
| Date |
Text |
| 2002-12-14 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 FUEL GAS | | | FBC-2001 CHAPTER 11 | | | | | | *****FROM PREVIOUS REVIEW | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2001 | | | GAS CODE. | | | B. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE BEING USED. | | | ********NEW COMMENT | | | 1) PLEASE VERIFY WITH GAS PROVIDER THE | | | DELIVERY PRESSURE. THEY DO NOT USEA | | | 1LB METER AND IF IT IS A 1LB SYSTEM THEN | | | ALL REGULATORS SHALL BE SHOWN ON GAS | | | RISER DIAGRAM. MANUFACTURE CUT SHEETS | | | FOR REGULATORS WILL BE REQUIRED, AND | | | A SHUT OFF VALVE AND UNION SHALL BE | | | SHOWN ON RISER. | | | 2) PLANS SHALL BE SUBMITTED AS COMPLETE | | | SETS. ALL OLD SHEETS SHALL BE REMOVED, | | | AND NEW SHEETS INSERTED. SUBMIT ON SET | | | OF OLD SHEETS TAKEN OUT FOR COMPARISON. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|