| 2002-11-07 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL CODE |
| | FBC-2001 CHAPTER 11 |
| | |
| | 1) SHT A1.0 PLEASE SUBMIT CALCULATIONS |
| | FOR MINIMUM FACILITIES PER TABLE 403.1. |
| | INDICATE IF SEATING IS FIXED, NOT FIXED, |
| | OR BOTH. NUMBER OF BOOTH SEATING. SEE |
| | TABLE 1003.1 FBC-2001 BUILDING. |
| | 2) SHT A2.0 SUBMIT MANUFACTURE INFORMAT- |
| | ION FOR WATER FILTER FOR ICE MACHINE. |
| | FILTER SHALL BE NSF APPROVED. |
| | 3) SHT A4.1 WATER RISER DIAGRAM. WATER |
| | HAMMER ARRESTORS SHALL BE LOCATED NEAR |
| | THE FIXTURE IN AN "EFFICTIVE RANGE" NOT |
| | AT TOP OF DROPS PER MANUFACTURE INSTALL- |
| | ATION AND PDI-WH 201. |
| | 4) SHT A4.1 GAS RISER, FOLLOWING INFOR- |
| | MATION REQUIRED FOR GAS PERMIT APPLICAT- |
| | ION. (SEPARATE GAS PERMIT REQUIRED) |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | GAS CODE. |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | C. TYPE OF GAS, (LP OR NATURAL) |
| | D. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2001 FUEL GAS CODE SEC |
| | 502 THRU 506. |
| | E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, & FBC-2001 |
| | FUEL GAS CODE SEC. 402.2. |
| | F. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND |
| | APPURTENANCES PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | G. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND |
| | APPURTENANCES PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | H. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |