| Plan Review Notes For Permit 02101578 |
| Permit Number |
02101578 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-11-15 00:00:00 | PROVISO: | | | | | | ADDITIONAL PERMITS REQUIRED FOR HOOD, | | | FIRESUPRESSION, AND WALK-IN COOLER. | | | PLEASE PROVIDE MANUFACTURER SUBMITTAL | | | & INSTALLATION INSTRUCTIONS WITH PERMIT | | | APPLICATION. | | | | | | HOOD SUBMITTAL - PROVIDE DETAIL OF | | | GREASE DUCT (TERMINATION, SLOPE, ACCESS | | | DOORS, ETC).SHOW COMPLIANCE WITH 2001 | | | FBC(M) SECTION 507 & 507 AS WELL AS | | | NFPA 96.PROVIDE AIR BALANCE.INDICATE | | | AIR MAKE-UP FOR HOOD. | | | | | | PLEASE NOTE AHU PIPING DETAIL DIAGRAM - | | | BULL-HEADING TEE IS NOT ALLOWED. | | | 2001 FBC(M) 1206.1.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. | | | NO MECHANICAL PLANS SUBMITTED FOR REVIEW |
|