2004-07-14 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE CORRELATE ALL A/ C LOADS
 AND LOAD CALCUALTIONS. PLEASE ALSO
 SEE LOADS SHOWN AT 65% DO NOT SEEM TO
 CORRELATE WITH WHAT IS INDICATED ON
 PANEL SCHEDULE. PLEASE SEE LOADS FOR A/C
 #2, OCP FOR COMP SHOWN LARGER THAN HEAT.
 THIS IS THE LOAD THAT NEEDS TO BE FIG.
 220.31A
 PLEASE ALSO SEE MIN OCP 125% AND MAX 150
 %.
  
 2)NOTE: PLEASE SEE REQUIRED DEDICATED
 CIRCUIT PER 210.52D,210.11C3 WHICH WAS
 REDLINED ON PREVIOUS PLANS WHICH WAS
 SHOWN AS 15A#14 IS NOW MISSING COMPLETE-
 -LY. PLEASE LIST. PLEASE SEE ABOVE FOR
 MIN REQUIRED TO BE #12, 20A.
  
 3)NOTE: PLEASE SEE TITLE BLOCK IS NOW
 SHOWN AS A FIRM. PLEASE PROVIDE PRINTED
 LICENSE #'S AS REQUIRED UNDER FS 481.219
 FAC 61G1-16.004.
 ORIGINAL PLANS INDICATES PLANS SHOWING
 ARCHITECT AS INDIVIDUAL ONLY.
  
 4)NOTE: PLEASE REVISE PLANS TO INCLUDE
 ORIG REDLINES.
  
 5)NOTE: PLEASE REVISE AND CORRELATE
 RISER DIAGRAM TO INCLUDE NEW SUB-PANEL
 "C" AND CORRELATE SIZES OF PANELS ON
 RISER AND PANELS. THIS HAS CHANGED FROM
 ORIG PLANS ALSO.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW