2002-12-24 00:00:00*************** UNSAT *****************
  
 PLEASE NOTE, SOME NOTES FROM FIRST
 REVIEW WERE NOT ADDRESSED.
  
 1)NOTE: PLEASE SEE 250-66 FOR SIZING OF
 GROUNDING ELECTRODE CONDUCTOR.
 MIN SIZE SHOULD BE #2, SHOWN AS #3.
  
 2)NOTE: PLEASE SHOW SIZE/AMERAGE OF
 METERCAN.
  
 3)NOTE: PLEASE SHOW EQUIPMENT GROUNDING
 CONDUCTORS BETWEEN MAIN DISC AND PANELS.
 SIZE PER 250-122.
  
 4)NOTE: PLEASE RECONFIGURE ALL LOAD
 CALCULATIONS, PLEASE NOTE A/C LOADS
 ARE NOT TAKEN AT 40% AS DONE ON PANEL "B
 PLEASE ALSO NOTE LOADS ON PANEL DO NOT
 CORRELATE. PLEASE GO OVER. PLEASE NOTE
 A/C LOAD IS SHOWN SEPARATE AND CORRECTLY
 ON PANEL "A", HOWEVER IT SEEMS THAT IT
 IS ALSO ADDED IN GENERAL LIGHTING LOAD?
 PLEASE CLARIFY HOW LIGHTING LOAD AT 3WAT
 -S PER SQ FT IS THE SAME ON BOTH PANELS?
  
 5)NOTE: PLEASE NOTE A SD IS ALSO REQ`D
 ON FIRST LEVEL OF A MULTI-LEVEL SFR
 NFPA-72 2-5.2.1.2
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  