| Plan Review Notes For Permit 02101569 |
| Permit Number |
02101569 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2002-12-24 00:00:00 | *************** UNSAT ***************** | | | | | | PLEASE NOTE, SOME NOTES FROM FIRST | | | REVIEW WERE NOT ADDRESSED. | | | | | | 1)NOTE: PLEASE SEE 250-66 FOR SIZING OF | | | GROUNDING ELECTRODE CONDUCTOR. | | | MIN SIZE SHOULD BE #2, SHOWN AS #3. | | | | | | 2)NOTE: PLEASE SHOW SIZE/AMERAGE OF | | | METERCAN. | | | | | | 3)NOTE: PLEASE SHOW EQUIPMENT GROUNDING | | | CONDUCTORS BETWEEN MAIN DISC AND PANELS. | | | SIZE PER 250-122. | | | | | | 4)NOTE: PLEASE RECONFIGURE ALL LOAD | | | CALCULATIONS, PLEASE NOTE A/C LOADS | | | ARE NOT TAKEN AT 40% AS DONE ON PANEL "B | | | PLEASE ALSO NOTE LOADS ON PANEL DO NOT | | | CORRELATE. PLEASE GO OVER. PLEASE NOTE | | | A/C LOAD IS SHOWN SEPARATE AND CORRECTLY | | | ON PANEL "A", HOWEVER IT SEEMS THAT IT | | | IS ALSO ADDED IN GENERAL LIGHTING LOAD? | | | PLEASE CLARIFY HOW LIGHTING LOAD AT 3WAT | | | -S PER SQ FT IS THE SAME ON BOTH PANELS? | | | | | | 5)NOTE: PLEASE NOTE A SD IS ALSO REQ`D | | | ON FIRST LEVEL OF A MULTI-LEVEL SFR | | | NFPA-72 2-5.2.1.2 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|