2002-11-05 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE ANY NECESSARY CHANGES
 TO THE PLANS ,AND RESUBMIT FOR REVIEW.
  
 1} INDICATE THE AMPERAGE RATING OF THE
 METER ENCLOSURE ON THE PLANS.
  
 2} THE 3-1/0 CONDUCTORS FEEDING
 PANEL"A"DO NOT COMPLY WITH TABLE
 310-15(B)(6) FOR 200 AMPS.THE SAME NOTE
 FOR THE 200 AMP DISCONNECT APPLIES.
  
 3} SERVICE CONDUCTORS PASSING THROUGH
 THE 150 AMP DISCONNECT MUST COMPLY WITH
 ARTICLE 373-8.
  
 4} THE GROUNDING ELECTRODE SYSTEM MUST
 COMPLY WITH ARTICLES 250-50 AND SIZED
 ACCORDING TO 250-66.PLEASE CHANGE THE
 RISER DIAGRAM TO REFLECT COMPLIANCE
 WITH THESE ARTICLES.
  
 5} PLEASE INDICATE BY WHAT MEANS THE
 EQUIPMENT GROUNDING CONDUCTOR IS BEING
 RAN FROM THE FIRST MEANS OF DISCONNECT
 TO THE PANELS.
  
 6} PLEASE NOTE BATH RECEPTACLES MUST
 COMPLY WITH THE SPACING REQUIREMENTS OF
 ARTICLE 210-52(D).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  