| Plan Review Notes For Permit 02101569 |
| Permit Number |
02101569 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-11-05 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION,MAKE ANY NECESSARY CHANGES | | | TO THE PLANS ,AND RESUBMIT FOR REVIEW. | | | | | | 1} INDICATE THE AMPERAGE RATING OF THE | | | METER ENCLOSURE ON THE PLANS. | | | | | | 2} THE 3-1/0 CONDUCTORS FEEDING | | | PANEL"A"DO NOT COMPLY WITH TABLE | | | 310-15(B)(6) FOR 200 AMPS.THE SAME NOTE | | | FOR THE 200 AMP DISCONNECT APPLIES. | | | | | | 3} SERVICE CONDUCTORS PASSING THROUGH | | | THE 150 AMP DISCONNECT MUST COMPLY WITH | | | ARTICLE 373-8. | | | | | | 4} THE GROUNDING ELECTRODE SYSTEM MUST | | | COMPLY WITH ARTICLES 250-50 AND SIZED | | | ACCORDING TO 250-66.PLEASE CHANGE THE | | | RISER DIAGRAM TO REFLECT COMPLIANCE | | | WITH THESE ARTICLES. | | | | | | 5} PLEASE INDICATE BY WHAT MEANS THE | | | EQUIPMENT GROUNDING CONDUCTOR IS BEING | | | RAN FROM THE FIRST MEANS OF DISCONNECT | | | TO THE PANELS. | | | | | | 6} PLEASE NOTE BATH RECEPTACLES MUST | | | COMPLY WITH THE SPACING REQUIREMENTS OF | | | ARTICLE 210-52(D). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/659-8096 EXT. 8392 |
|