Plan Review Notes
Plan Review Notes For Permit 02101507
Permit Number 02101507
Review Stop P
Sequence Number 4
Notes
Date Text
2003-05-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) FLOOR SINKS ARE REQUIRED FOR ALL
 SINKS IN THE FOOD PREP AREAS.
 2) ALL FLOOR SINKS THAT HAVE INDIRECT
 WASTE SHALL BE LOCATED SO AS NOT TO BE A
 TRIPPING HAZARD.
 3) FLOOR DRAINS REQUIRED FOR GENERAL
 CLEAN UP AREAS. (TO CLEAN FLOOR)
 4) ALL FILTERS SHALL BE NSF APPROVED.
 MANUF. INFO REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692