Plan Review Notes
Plan Review Notes For Permit 02101507
Permit Number 02101507
Review Stop P
Sequence Number 2
Notes
Date Text
2002-12-27 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) ACKNOWELEGED RESPONSE TO COMMENT #1,
 STAMPED PLAN BY HOTEL AND RESTURANT DIV
 REQUIRED WILL STILL BE REQUIRED FOR
 PUBLIC RECORD AND ON JOBSITE AS SOON AS
 POSSIBLE.
 2) FROM PREVIOUS REVIEW: ALL INDIRECT
 WASTE SHALL DRAIN INTO A FLOOR SINK,
 ITEMS #3 (2) AND # 15.1 STILL DRAIN INTO
 A TROUGH.
 3) FROM PREVIOUS REVIEW: EXPANSION CON-
 TROL FOR WATER HEATER IS NOT ACCOMPLISH-
 ED BY USE OF A PRESSURE REDUCING VALVE.
 AN EXPANSION TANK IS REQUIRED AT WATER
 HEATER.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377