| Plan Review Notes For Permit 02101507 |
| Permit Number |
02101507 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-12-27 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | 1) ACKNOWELEGED RESPONSE TO COMMENT #1, | | | STAMPED PLAN BY HOTEL AND RESTURANT DIV | | | REQUIRED WILL STILL BE REQUIRED FOR | | | PUBLIC RECORD AND ON JOBSITE AS SOON AS | | | POSSIBLE. | | | 2) FROM PREVIOUS REVIEW: ALL INDIRECT | | | WASTE SHALL DRAIN INTO A FLOOR SINK, | | | ITEMS #3 (2) AND # 15.1 STILL DRAIN INTO | | | A TROUGH. | | | 3) FROM PREVIOUS REVIEW: EXPANSION CON- | | | TROL FOR WATER HEATER IS NOT ACCOMPLISH- | | | ED BY USE OF A PRESSURE REDUCING VALVE. | | | AN EXPANSION TANK IS REQUIRED AT WATER | | | HEATER. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|