| Plan Review Notes For Permit 02101507 |
| Permit Number |
02101507 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-12-18 00:00:00 | ************* UNSAT ******************** | | | | | | 1)NOTE: PLEASE NOTE, "SHOW WINDOW" | | | RECEPTS WILL BE REQ`D PER 210-62 AND | | | ART 100 OF NEC. IT WAS NOTED THAT PLANS | | | SHOW A NOTE MENTIONONG THAT NO RECEPTS | | | ARE REQ`D. PLEASE NOTE, ALMOST ALL REST/ | | | FAST FOOD/FOOD SERVICE ETC HAVE A MEANS | | | TO ADVERTISE IN WINDOWS, THEREFORE MEET- | | | ING ART 100. SMALL WINDOW SIGNS ETC ARE | | | USED AND RECEPTS IN "SHOW" WINDOWS | | | PREVENT THE USED OF EXTENSION CORDS | | | BEING USED IN A MANOR THAT WOULD CREATE | | | A FIRE AND/OR LIFE SAFETY ISSUE. | | | | | | 2)NOTE: PLEASE SEE 450-13B FOR SIZING | | | OF PERMITTED TRANSFORMERS ABOVE CEILING. | | | PLEASE NOTE, UP TO 50 KVA ONLY. | | | PLEASE ADDRESS. | | | | | | 3)NOTE: PLEASE SEE 240-21 FOR TAPPED | | | CONDUCTORS FROM TRANSFORMER. EITHER | | | PRIMARY/PLUS SECONDARY OR 10'FT MAX. | | | | | | 4)NOTE: PLEASE NOTE NO CONTINUOUS | | | EQUIPMENT GROUND IS SHOWN FROM SECONDARY | | | SIDE OF TRANSFORMER TO PANEL? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|