| Date |
Text |
| 2002-11-13 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 11 |
| | |
| | 1) PLEASE ROUTE PLANS TO DEPT. OF BUSIN- |
| | ESS REGULATION HOTEL AND RESTURAND DIV. |
| | (954) 956-5692 FOR REVIEW PRIOR TO RE- |
| | SUBMITTING TO CITY FOR REVIEW. |
| | 2) SHT D-1 DEMO NOTES #4 & 5, ALL CAPPED |
| | LINES (WATER & SANT.) SHALL BE INSPECTED |
| | PRIOR TO COVERING. |
| | 3) SHT EQ-1 EQUIPMENT SCHEDULE, ITEMS |
| | #7, 19, 21, 37, 43, 47, 49, & 50 DO NOT |
| | SHOW EITHER WATER SUPPLY, WASTE, (DIRECT |
| | OR INDIRECT), OR BOTH. PLEASE CLAIRFY. |
| | 4) SHT A-1 TABLE 403.1 REQUIRES A DRINK- |
| | ING FOUNTAIN. |
| | 5) SHTS P-1/P-2 (SANT RISER) ALL IN- |
| | DIRECT WASTE SHALL BE DISCHARGED INTO A |
| | FLOOR SINK. FLOOR DRAINS, & TROUGH DRAIN |
| | IS NOT AN APPROVED INDIRECT WASTE RE- |
| | CEPTOR. SEC 802.3 - PLEASE PROVIDE FLOOR |
| | SINKS FOR ALL INDIRECT WASTES AND LOCATE |
| | THEM SO THEY WILL NOT BE TRIPPING HAZARD |
| | 6) SHT P-1 BIG DIPPER GREASE TRAP IS NOT |
| | APPROVED FOR THIS SPACE. A GREASE LINE |
| | IS AVAILABLE FOR USE IN 700 S ROSEMARY |
| | BLDG. PLEASE CHECK WITH CITY PLACE MAN- |
| | AGEMENT. |
| | 7) SHT P-1 AN RPZ BACKFLOW IS REQUIRED |
| | FOR THIS SPACE. MAXIMUM HEIGHT A.F.F. IS |
| | 4' FOR SERVICING AND TESTING. |
| | 8) SHT P-1 DISHWASHER, ITEM #8 SHALL |
| | DISCHARGE INTO THE SANITARY SYSTEM, NOT |
| | THE GREASE WASTE SYSTEM AS SHOWN. PER |
| | UTILITY DEPT. (ALSO SHOW ON SANITARY/ |
| | GREASE RISERS SHT P-2) |
| | 9) SHT P-1 ALL FOOD HANDLING EQUIPMENT |
| | AND CLEAR WASTE WATER SHALL DISCHARGE |
| | THROUGH AN INDIRECT WASTE PIPE AS SPECI- |
| | FIED IN SECTIONS 802.1.1 THROUGH 802.1.4 |
| | 10) SHTS P-1/P-2WATER HEATER PAN DRAIN |
| | AND RELIEF LINE SHALL DRAIN INTO A FLOOR |
| | SINK NOT FLOOR DRAIN AS SHOWN ON FLOOR |
| | PLAN AND HEATER DETAIL. |
| | 11) SHT P-2 WATER HEATER DETAIL, THERMAL |
| | EXPANSION CONTROL IS REQUIRED PER 607.3 |
| | AND 607.3.2. PLEASE SHOW ON DETAIL. |
| | 12) SHT P-2 PLEASE SUBMIT CALCULATIONS |
| | FOR WATER SUPPLY FOR FIXTURES. 3/4" FOR |
| | ALL FIXTURES. |
| | 13) SHT P-3 "NOTE" STATES ALL INDIRECT |
| | WASTE TO FLOOR DRAINS, PLEASE SHOW ALL |
| | INDIRECT TO FLOOR SINKS. |
| | |
| | REVIEW BY KEN STEVENS |