| Plan Review Notes For Permit 02101507 |
| Permit Number |
02101507 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-11-26 00:00:00 | DENIED: | | | | | | PLEASE CLARIFY THE FOLLOWING: | | | | | | 1.DRAIN PAN WITH OVERFLOW PROTECTION | | | REQUIRED AS PER 2001 FBC(M) 307.2.3. | | | | | | 2.PLEASE IDENTIFY CONDENSATE DRAIN | | | (LINE SIZE & MATERIAL). INDICATE | | | TERMINATION (EXISTING?) | | | | | | 3.CONDENSER UNIT STANDS SHALL COMPLY | | | WITH 2001 FBC TABLE 1511.7 (SEE | | | ATTACHED). | | | | | | PLEASE NOTE ADEQUATE ACCESS REQUIRED FOR | | | INSPECTION, SERVICE & REPLACEMENT OF THE | | | AHU. | | | | | | ADDITIONAL PERMIT REQUIRED FOR WALK-IN | | | COOLERS/FREEZERS.PLEASE PROVIDE | | | MANUFACTURER SUBMITTAL DATA WITH PERMIT | | | APPLICATION. |
|