2002-11-26 00:00:00DENIED:
  
 PLEASE CLARIFY THE FOLLOWING:
  
 1.DRAIN PAN WITH OVERFLOW PROTECTION
 REQUIRED AS PER 2001 FBC(M) 307.2.3.
  
 2.PLEASE IDENTIFY CONDENSATE DRAIN
 (LINE SIZE & MATERIAL). INDICATE
 TERMINATION (EXISTING?)
  
 3.CONDENSER UNIT STANDS SHALL COMPLY
 WITH 2001 FBC TABLE 1511.7 (SEE
 ATTACHED).
  
 PLEASE NOTE ADEQUATE ACCESS REQUIRED FOR
 INSPECTION, SERVICE & REPLACEMENT OF THE
 AHU.
  
 ADDITIONAL PERMIT REQUIRED FOR WALK-IN
 COOLERS/FREEZERS.PLEASE PROVIDE
 MANUFACTURER SUBMITTAL DATA WITH PERMIT
 APPLICATION.