Plan Review Notes
Plan Review Notes For Permit 02101507
Permit Number 02101507
Review Stop E
Sequence Number 1
Notes
Date Text
2002-10-31 00:00:00************* UNSAT *****************
  
 1)NOTE: PLEASE NOTE RISER DIAGRAM NEEDS
 MORE INFORMATION FOR COMPLETE REVIEW.
 PLEASE NOTE MISSING WIRE AND CONDUIT
 FROM X-FORMER TO PANEL "A".
  
 2)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNDING CONDUCTORS IN CONDUITS TO AND
 FROM TRANSFORMER. PLEASE CLARIFY METHOD
 OF EQUIPMENT GROUND BETWEENGUTTER AND
 PANEL "H". SIZE PER 250-122, PER 250-24
  
 3)NOTE: PLEASE CLARIFY 75KVA TRANSFORMER
 BELOW CEILING. PER 450-13
  
 4)NOTE: PLEASE CLARIFY NEW/EXISTING
 SHOW WINDOW RECEPTS PER 210-62
  
 5)NOTE: PLEASE CLARIFY SIGN CIRCUIT PER
 600-5.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372