| Plan Review Notes For Permit 02101507 |
| Permit Number |
02101507 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-10-31 00:00:00 | ************* UNSAT ***************** | | | | | | 1)NOTE: PLEASE NOTE RISER DIAGRAM NEEDS | | | MORE INFORMATION FOR COMPLETE REVIEW. | | | PLEASE NOTE MISSING WIRE AND CONDUIT | | | FROM X-FORMER TO PANEL "A". | | | | | | 2)NOTE: PLEASE NOTE MISSING EQUIPMENT | | | GROUNDING CONDUCTORS IN CONDUITS TO AND | | | FROM TRANSFORMER. PLEASE CLARIFY METHOD | | | OF EQUIPMENT GROUND BETWEENGUTTER AND | | | PANEL "H". SIZE PER 250-122, PER 250-24 | | | | | | 3)NOTE: PLEASE CLARIFY 75KVA TRANSFORMER | | | BELOW CEILING. PER 450-13 | | | | | | 4)NOTE: PLEASE CLARIFY NEW/EXISTING | | | SHOW WINDOW RECEPTS PER 210-62 | | | | | | 5)NOTE: PLEASE CLARIFY SIGN CIRCUIT PER | | | 600-5. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|