2002-11-05 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02101504
 ADD: 720 KAYE STREET
 CONT: JAMES T. WADSWORTH JR
 TEL: (561)421-1742
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION
 ANDREMOVE AND REPLACE ANY PAGES AS
 NECESS- ARY. A TRANSMITTAL LETTER
 LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 1) CORRECTION: SHEET A-1 GENERAL NOTES,
 NOTE:1) WINDOWS AND EXTERIOR DOORS
 RECEIVE APPROVED SHUTTER PER FBC 2315?
 PLEASE CORRECT CODE SECTION, THIS
 REFERSTO HIGH WIND HURRICANE ZONES,
 DADE /
 BROWARD CONTIES.
  
 2) CORRECTION: SHEET A-1 GENERAL NOTES,
 NOTE:2) EGRESS WINDOWS SHALL MEET
 THEREQUIREMENTS OF FBC 3122B, CORRECT!!!
  
 3) SOIL STATEMENT CLARIFY,2500LBS/ SQ
 FTBY RATIONAL ANLYSIS, EXPLAIN TESTING
 PROCEDURES TO ACHIEVE THIS VALUE?
  
 4) PERMIT VALUE: VALUE IS LOW, VALUATION
 RATES FOR SUCH PERMIT FEES SHALL BE
 BASED ON, STANDARD BUILDING CODE EVALUA-
 TION TABLES LATEST EDITION, CITY CODE
 ORDANANCE # 3355-00.SUCH PERMIT FEES
 SHALL INCLUDE ALL MATERIALS, LABOR AND
 ASSOCIATED FEES, TOTAL COST OF JOB. THIS
 WILL BE DETERMINED AT THE TIME OF PLAN
 APPROVAL.
 LAND VALUE $36,300.00
 IMPROVEMENT VALUE 95,885.00
 DEPENDING ON THE CALCULATED VALUE
 OF THE JOB SEC 3407.1.7.2 WILL ESTABLISH
 TO WHAT EXTENT THE BUILDING SHALL BE
 MADE TO CONFORM TO THE CURRENT CODE.
  
 5) THE PLANS DO NOT INDICATE THE TOTAL
 SCOPE OF WORK THAT SHALL BE REQUIRED,
 ADDITONS THAT WERE PARTIALLY ENCLOSED,
 THE SIZE OF EXISTING OPENINGS VS THE
 NEW SIZES. AREAS OF THE BUILDING THAT
 HAVE NO FOUNDATION, DISCOVERED THROUGH A
 FIELD INVESTIGATION BY CHIEF INSPECTOR
 LOU HATTEN.
  
 6)PROVIDE ENERGY CALCULATIONS AND
 EQUIPMENT SIZING CALCULATIONS (MANUAL J)
 AS REQUIRED BY THE 2001 FLORIDA ENERGY
 EFFICIENTCY CODE FOR BUILDING CONSTRUC-
 TION. PLANS INDICATE NO ADDITIONAL A/C
 SQ FT. INDICATE A/C FOR THE 1ST FLOOR
 LIVING AREA, THIS IS SUPPOSEDLY NEW
 WORK.
  
 7) SHEET GN-1 PLYWOOD FASTENING SCHEDULE
 DELETE ANY REFRENCES TO SEMCO PRODUCTS,
 THEY ARE OUT OF BUSINESS. REFRENCE TO
 GUN NAILS IF THEY ARE A SMALLER DIA.
 THAN 0.131" THE MANUFACTURER IS TO SPEC-
 IFY WHAT THE EQUIVELENT SPACING SHALL BE
  
 8) PLANS ARE MISSING THE FLOOR & CEILING
 JOIST LAYOUT FOR THE FIRST & SECOND
 FLOOR PLUS THE INTERIOR BEARING WALLS.
  
 9) SHEET A-1 LOWER LEFT DETAIL,
 ROOF FRAMING @ COVERED ENTRY, MISSING
 INFORMATION, DETAIL OF NEW MAIN ENTRY,
 HEADER SIZE SPECIES OF WOOD, THE AMOUNT
 OF FULL STUDS REQUIRED, JACK STUDS, THE
 UPLIFT LOADS, GRAVITY LOADS, THE ANCHOR-
 ING REQUIREMENTS.
 THE DETAIL INDICATES 5/8" ANCHORBOLT
 BUT NOT THE LENGTH? THERE IS NO INFORMA-
 TION ON THE SIZE OF THE GIRDER TRUSS,
 SINGLE MEMBER OR DOUBLE, HEIGTH OF THE
 GIRDER? THE STEEL COLUMN DOESN'T INDI-
 CATE THE WIDTH OF THE SEAT.
 DETAIL 3/A-2, 4/A-2 ARE NOT INDICATED
 WHERE THEY ARE TO BE USED, OR THE LOADS
 TO BE IMPOSED ON THEM? THE ENTRY DETAIL
 DOESN'T INDICATE HOW THE GIRDERS ENDING
 AT THE EXISTING STRUCTURE ARE TO BE SUPP
 ORTED?
  
 10) AS INDICATED ON THE PLAN "NO FOUINDA
 TION" PLEASE PROVIDE HOW STRUCTURE SHALL
 BE SHORED UP WHILE FOUNDATION IS CON-
 STRUCTED, GIVE SHORING AND FOUNDATION
 DETAIL WITH FOOTING SIZE, STEEL AND
 ANCHORING.
  
 11) NEW STAIRWAY, 1007.3.1 THE SUM OF
 2 RISERS + 1 TREAD SHALL EQUAL BETWEEN
 14" & 25". THE PLAN ALSO INDICATES THE
 USE OF 14 RISERS @ 6"= 84". THE CEILING
 HEIGTH IS 7'-8" OR 92" PLUS THE FLOOR
 JOIST AND FLOORING OF 2ND FLOOR?
  
 12) EXISTING PATIO, NO NEW WORK, FIELD
 INVESTIGATION, INDICATES A 30" CBS WING
 WALL, WITH A OPEN SCREEN PORCH, WITH A
 2X6" OPEN PLANK CEILING, NO INFORMATION
 IS GIVEN ON THE ENCLOSING OF THIS STRUC-
 TURE, NOR INFORMATION ON THE RESISTEING
 OF UPLIFT ON THE EXISTING STEM WALL?
 THIS AREA TO BE A/C? THE EXISTING ROOF
 SHEATHING THICKNESS, SPACING OF RAFTERS,
 NOR THE ANCHOR REQUIUREMENTS OF THE
 FRAME WALL, RAFTERS NOR LEDGER?
  
 13) FRONT ELEVATION, 2ND FLOOR, THERE IS
 NO DETAILS OF THE FRAMING ABOVE THE NEW
 WINDOWS NOR ANCHOR REQUIREMENTS, NO IN-
 FORMATION ON THE DECORATIVE ADDITON TO
 THE PARAPET.
  
 14)1503.3 COPING. PARARET WALLS SHALL
 BE PROPERLY COPED WITH NONCOMBUSTIBLE
 MATERIALS OF A WIDTH NO LESS THAN THE
 THICKNESS OF THE PARAPET WALL.
  
 15) RIGHT ELEVATION SHED ROOF EXISTING
 FOR WATER HEATER, NOT ENCLOSED, GIVE
 ADDITIONAL INFORMATION AS LISTED UNDER
 COMMENT # 12.
  
 16) EXTERIOR ENTRY TO 2ND FLOOR, INDI-
 CATE HOW THE ARCHED ROOF AND CEILING
 ARE TO BE ENCORPORATED WITH THE ARCHED
 WINDOWS OF THE SIDE VIEW?
  
 17)1503.4 ROOF DRAINS UNLESS ROOFS ARE
 SLOPED TO DRAIN OVER THE ROOF EDGE, ROOF
 DRAINS SHALL BE INSTALLED AT THE LOWEST
 POINT OF THE ROOF. WHERE REQUIRED FOR
 ROOF DRAINAGE,SCUPPERS SHALL BE LOCATED
 AS DETERMINED BY THE ROOF SLOPE AND CON-
 TRIBUTING ROOF AREA.
  
 18)1503.4.2 OVERFLOW DRAINS SHALL BE
 THE SAME SIZE AS ROOF DRAINS, INSTALLED
 WITH THE INLET FLOW LINE LOCATED 2"
 ABOVE THE LOWEST POINT OF THE ROOF LINE.
 OVERFLOW SCUPPERS SHALL BE A MINIMUM OF
 4"IN HEIGTH AND SHALL BE PLACED IN WALLS
 OR PARARETS WITH THE INLET FLOW LINE
 NOT LESS THAN 2" ABOVE THE ROOF SURFACE.
  
 19) 1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 20) FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE"B" NOT D
 4)- INTERNAL PRESSURE COEFFICIENT, 0.18
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 ALSO WIND PRESSURE ASCE 7-98!
  
 21) WINDOWS INDICATED ON PLAN ARE TO BE
 CASEMENT WINDOWS, INDICATE THE CLEAR
 OPENING SIZE OF THESE WINDOWS, INDICATE
 THE HINGE SIDE FOR CASEMENT WINDOW?
  
 22)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
  
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.MISSING REPORTS:
 A) WINDOWS
 B) DOORS
 C) MULLIONS
 D) STORM SHUTTERS
 E)ROOFING ASSEMBLIES
  
 23)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED.
  
 24) 1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 25) 1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 26)PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
  
 27)FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
 28)FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 29) 1606.4.4 ANCHOR METHODS. PROVIDE
 INFORMATION FOR INSTALLATION OF DOOR
 AND WINDOW BUCKS.
  
 30) 1707.4.4.1 ANCHOR REQUIREMENTS:
 WINDOW & DOOR ASSEMBLIES SHALL BE ANCHOR
 ED IN ACCORDANCE WITH THE PUBLISHED
 MANUFACTURER'S RECOMMENDATIONS TO
 ACHIEVE THEDESIGN PRESSURE SPECIFIED.
 SUBSTITUTE ANCHORING SYSTEM USED FOR
 THE SUBSTRATE NOT SPECIFIED BY THE
 FENESTRATION MANUFACTURER SHALL PROVIDE
 EQUAL OR GREATER ANCHORING AS DEMONSTRA-
 TED BY ACCEPTED ENGINEERING PRACTICES.
  
 31) INDICATE THE USAGE OF 2/D-1 THIS DE-
 TAIL CAN NOT BE USED FOR ANY BEARING
 WALL, NOT INDICATED ON FLOOR PLAN!
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026