Plan Review Notes
Plan Review Notes For Permit 02101495
Permit Number 02101495
Review Stop E
Sequence Number 1
Notes
Date Text
2002-10-24 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE A LOAD CALCULATION FOR
 THE EXISTING SERVICE.ALSO VERIFY THAT
 NAMEPLATE RATING MATCHES ASSUMED LOAD
 FOR THE ADDED SERVICE.
 NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 THESE ITEMS NEED TO BE SUBMITTED BEFORE
 ROUGH INSPECTION.IF THERE ARE ANY
 QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392