Plan Review Notes
Plan Review Notes For Permit 02101374
Permit Number 02101374
Review Stop P
Sequence Number 1
Notes
Date Text
2002-11-12 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) SHT A-1 ALL DEMO OF PLUMBING SHALL BE
 INSPECTED PRIOR TO COVERING.
 2) SHT A-1 WORK ROOM SINK SHALL COMPLY
 WITH 11-4.24 AND ALL SUBSECTIONS. PLEASE
 PROVIDE A DETAIL.
 3) SHT A-1 TABLE 403.1 REQUIRES A DRINK-
 ING FOUNTAIN. PLEASE GIVE DETAIL FOR
 DRINKING FOUNTAIN SHOWING COMPLIANCE OF
 SECTION 11-4.15 AND ALL SUBSECTIONS.
 SECTION 11-4.1.3(10)(A) FOR THOSE WHO
 HAVE DIFFICULTY BENDING OR STOOPING.
 ALSO SEE SECTION 410.1.
 4) SHT A-1 PLEASE GIVE DIMENSIONS FOR
 BATHROOM. SHOW 5' TURNING RADIUS REQUIR-
 ED PER SECTION 11-4.22.3
 5) SHT A-1 SHOWER SHALL BE ACCESSIBLE.
 PLEASE PROVIDE DETAIL PER SEC 11-4.21
 AND ALL SUBSECTIONS.
 6) SHT A-1 WATER HEATER SHALL COMPLY
 WITH SECTION 504.7.1. DISCHARGE FROM
 RELIEF VALVE SHALL NOT ANY TRAPPED SECT-
 IONS AND SHALL HAVE A VISIBLE AIR GAP.
 ALSO SECTIONS 504.8 AND 504.8.1 HEATER
 EMERGENCY PAN AND DRAIN. PLEASE SHOW
 DETAILS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377