| Plan Review Notes For Permit 02101336 |
| Permit Number |
02101336 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2002-12-19 00:00:00 | ***************UNSAT ************ | | | | | | 1)NOTE: PLEASE NOTE, NOT ALL NOTES FROM | | | PREVIOUS REVIEWS ARE COMPLETE, PLANS | | | STILL SHOW A NEW? PANEL ON E-2 THAT IS | | | NOT CLARIFIED??RISER DIAGRAM IS THE | | | SMAE ONE SUBMITTED PREVIUOUSLY EXCEPT | | | THERE IS NO D-1SHOWN THISTIME? | | | PLEASE ONLY SHOW EQUIPMENT PERTAINING | | | TO THIS SPACE. | | | | | | 2)NOTE: PLEASE NOTE UNDER FS/FAC ANY | | | ADDTIONAL PAPER SUBMITTED W/ARCH SEAL | | | AND SIGNATURE MUST ALSO CONTAIN TITLE | | | BLOCK AS REQ`D BY FS. 61G1-16.004. | | | WORK MUST BE DONE BY ARCH OF RECORD. | | | | | | 3)NOTE: PLEASE NOTE ALL CONTINUOUS LOADS | | | ARE TO BE SHOWN AT 125%. 215-3,230-42 | | | | | | 4)NOTE: PLEASE SEE LETTER ATTACHED WITH | | | RESPECT TO DESIGN PROFESSIONALS. | | | 553.80(2) (B). | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|