Notes
Date Text
2002-12-19 00:00:00***************UNSAT ************
  
 1)NOTE: PLEASE NOTE, NOT ALL NOTES FROM
 PREVIOUS REVIEWS ARE COMPLETE, PLANS
 STILL SHOW A NEW? PANEL ON E-2 THAT IS
 NOT CLARIFIED??RISER DIAGRAM IS THE
 SMAE ONE SUBMITTED PREVIUOUSLY EXCEPT
 THERE IS NO D-1SHOWN THISTIME?
 PLEASE ONLY SHOW EQUIPMENT PERTAINING
 TO THIS SPACE.
  
 2)NOTE: PLEASE NOTE UNDER FS/FAC ANY
 ADDTIONAL PAPER SUBMITTED W/ARCH SEAL
 AND SIGNATURE MUST ALSO CONTAIN TITLE
 BLOCK AS REQ`D BY FS. 61G1-16.004.
 WORK MUST BE DONE BY ARCH OF RECORD.
  
 3)NOTE: PLEASE NOTE ALL CONTINUOUS LOADS
 ARE TO BE SHOWN AT 125%. 215-3,230-42
  
 4)NOTE: PLEASE SEE LETTER ATTACHED WITH
 RESPECT TO DESIGN PROFESSIONALS.
 553.80(2) (B).
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESIONS,
 PLEASE CALL.
  