Plan Review Notes
Plan Review Notes For Permit 02101336
Permit Number 02101336
Review Stop E
Sequence Number 2
Notes
Date Text
2002-11-21 00:00:00************ UNSAT ****************
  
 ** PLEASE NOTE, NOT ALL NOTES FROM FIRST
 REVIEW WERE ADDRESSED AND NOW A COMPLETE
 -LY NEW RISER DRAWING WAS SUBMITTED ON
 E-3???
  
 1)NOTE: PLEASE NOTE, AIC RATINGS FOR
 ALL NEW EQUIPMENT. 110-9/215-5
 NEW RISER SHOWS NEW AND RELOCATED WORK
 WITH NO CLEAR VIEW ON WHERE ALL THESE
 ITEMS ARE LOCATED? PLEASE PROVIDE AN
 OVER VIEW FOR NEW/EXSITING ELECTRICAL
 ROOM(S) THAT THESE ITEMS ARE GOING IN.
 PLEASE NOTE A NEW PANEL IS BEING ADDED
 AND IS SHOWN ON E-1 BUT WHICH PANEL IS
 THIS ON RISER DIAGRAM?
 LOADS FROM DISC`S ARE SHOWN GOING BACK
 INTO A GUTTER THAT IS BEING TAPPED AGIAN
 ??
 PLEASE PROVIDE A SINGLE -LINEDIAGRAM
 THAT SHOWS LAYOUT.
 PLANS SHOW ONE NEW PANEL AND RISER SHOWS
 MORE?
  
 2)NOTE: PLEASE SHOW CIRCUITING AND
 CORRELATE W/ PANEL SCHEDULES AS NOTED
 ON FIRST REVIEW.
  
 3)NOTE: PLEASE SEE NOTE FROM FIRST
 REVIEW FOR CIRCUITING OF EM/EX LTS PER
 700-12E. THEY ARE SHOWN AS BEING ON
 SEPARATE CIRCUITS FROM LTS.
  
 4)NOTE:PLEASE CLARIFY WHERE RECEPT LOADS
 ARE IN LOAD CALCULATIONS. 220-13
 NOT FROM 220-11.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL. IF AN APPOINTMENT IS NEEDED
 PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372