| 2002-11-21 00:00:00 | ************ UNSAT **************** |
| | |
| | ** PLEASE NOTE, NOT ALL NOTES FROM FIRST |
| | REVIEW WERE ADDRESSED AND NOW A COMPLETE |
| | -LY NEW RISER DRAWING WAS SUBMITTED ON |
| | E-3??? |
| | |
| | 1)NOTE: PLEASE NOTE, AIC RATINGS FOR |
| | ALL NEW EQUIPMENT. 110-9/215-5 |
| | NEW RISER SHOWS NEW AND RELOCATED WORK |
| | WITH NO CLEAR VIEW ON WHERE ALL THESE |
| | ITEMS ARE LOCATED? PLEASE PROVIDE AN |
| | OVER VIEW FOR NEW/EXSITING ELECTRICAL |
| | ROOM(S) THAT THESE ITEMS ARE GOING IN. |
| | PLEASE NOTE A NEW PANEL IS BEING ADDED |
| | AND IS SHOWN ON E-1 BUT WHICH PANEL IS |
| | THIS ON RISER DIAGRAM? |
| | LOADS FROM DISC`S ARE SHOWN GOING BACK |
| | INTO A GUTTER THAT IS BEING TAPPED AGIAN |
| | ?? |
| | PLEASE PROVIDE A SINGLE -LINEDIAGRAM |
| | THAT SHOWS LAYOUT. |
| | PLANS SHOW ONE NEW PANEL AND RISER SHOWS |
| | MORE? |
| | |
| | 2)NOTE: PLEASE SHOW CIRCUITING AND |
| | CORRELATE W/ PANEL SCHEDULES AS NOTED |
| | ON FIRST REVIEW. |
| | |
| | 3)NOTE: PLEASE SEE NOTE FROM FIRST |
| | REVIEW FOR CIRCUITING OF EM/EX LTS PER |
| | 700-12E. THEY ARE SHOWN AS BEING ON |
| | SEPARATE CIRCUITS FROM LTS. |
| | |
| | 4)NOTE:PLEASE CLARIFY WHERE RECEPT LOADS |
| | ARE IN LOAD CALCULATIONS. 220-13 |
| | NOT FROM 220-11. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. IF AN APPOINTMENT IS NEEDED |
| | PLEASE CALL. |
| | |
| | |