2002-10-24 00:00:00*********** ***** UNSAT **************
  
 1)NOTE: PLEASE SSHOW CIRCUITING ON PLANS
 AND CORRELATE WITH SUBMITTED PANEL
 SCHEDULE.
  
 2)NOTE: PLEASE NOTE, PANEL SCHEDULE IS
 SHOWN BLANK W/ NO INFORMATION??
 PLEASE PROVIDE INFORMATION FOR PANEL.
 PLANS SHOW NEW PANEL? WHERE, HOW IS
 PANEL BEING FED??
 215-5, SEE 110-9 AND SUBMIT AIC RATING
 FOR ANY NEW MAINS/PANELS.
  
 3)NOTE; PLEASE SEE 700-12 FOR CIRCUITING
 OF EM LTS AND EXIT LTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372