| 2006-01-20 00:00:00 | ************ UNSAT ************ |
| | |
| | |
| | 1)NOTE: PLEASE CORRELATE ALL CIRCUITING |
| | ON PLANS WITH PANEL SCHEDULES. |
| | PLEASE SEE LTS ON SMALL APPL, LTS ON |
| | DRYER, BATHS, KIT, APPLIANCES, ETC ETC. |
| | PLEASE SEE THERE ARE FAR TOO MANY TO |
| | WRITE UP OR REDLINE. PLEASE SEE MANY OF |
| | THESE WERE REDLINED, HOWEVER BY NO MEANS |
| | ALL. |
| | |
| | 2)NOTE: PLEASE SEE SMOKE DETECTORS'S |
| | SHOWN ON THREE OR MORE CIRCUITS. PLEASE |
| | SEE NFPA-72 8-1 WHICH REQUIRES SD'S TO |
| | BE WIRED "IN-LINE". IF WIRED IN-LINE, |
| | THEN THESE CAN NOT BE ON MORE THAN ONE |
| | CIRCUIT. ALSO SHOWN ON MULTIPLE PANELS. |
| | |
| | 3)NOTE: PLEASE SEE 210.52D,210.11C3, |
| | WHICH REQUIRES ALL BATH(S) CIRCUIT(S) |
| | RECEPTS TO BE ON A MIN OF 20A AND #`12. |
| | PLEASE SEE CIRCUITING AS MANY ARE SHOWN |
| | ON OTHER CIRCUITS WHICH ARE 15A AND #14 |
| | AWG. |
| | |
| | 4)NOTE: PLEASE CORRELATE ALL POOL |
| | EQUIPMENT ON PLANS WITH PANEL SCHEDULES |
| | AND LOAD CALCUALTIONS. PLEASE SEE |
| | CIRCUITING ON PLANS IS ALSO SHOWN AS |
| | COND UNITS.?? |
| | PLEASE SEE PLANS SHOW TWO ELEC POOL |
| | HEATERS, HOWVER PANEL SCHEDULE SHOWS |
| | ONE?? |
| | PLEASE ALSO SEE ALL CONTINUOUS LOADS |
| | SUCH AS POOL HEATER AND POOL PUMP SHALL |
| | BE SHOWN AT 125%. 215.3,230.42, |
| | PLEASE SEE MIN OCP SHALL BE SIZED AT |
| | 125% PER 680.9. PLEASE PROVIDE KW |
| | RATINGS FOR POOL HEATERS. |
| | |
| | 5)NOTE: PLEASE SEE PLANS, CLEARENCES FOR |
| | CU DISCONNNECTS DO NOT MEET 110.26. |
| | PLEASE ALSO SEE ANY AHU'S WHICH APPEAR |
| | TO SHOW SHELVING DIRECTLY INFRONT OF |
| | THESE DISCONNECTS AND UNITS. |
| | |
| | 6)NOTE: PLEASE SEE CORRELATE PANEL |
| | SCHEDULES AND RISER DIAGRAM. PLEASE SEE |
| | ALL PANELS INDICATE MAINS (A |
| | GARAGE PANEL REQUIRED) HOWEVER PANELS |
| | FOR POOL PANEL AND PANEL C SHOWS MLO ON |
| | SCHEDULE AND SHOWS MAIN DISCONNECT ON |
| | RISER?? PLEASE CORRELATE. |
| | 215.5 |
| | |
| | 7)NOTE: PLEASE SEE PLANS SHOWS POOL |
| | PANEL AND A PANEL "D"?? |
| | PLEASE CORRELATE.215.5 |
| | |
| | 8)NOTE: PLEASE SEE CIRCUITS SHOWN ON |
| | PLANS AS GEN LTS, PELASE SEE CIRCUITING |
| | SHALL BE SPECIFIC TO AREA/ROOMS. |
| | 215.5, 408.4 |
| | |
| | 9)NOTE: PLEASE SEE KITCHEN AREA WHERE |
| | APPEARS TO BE A MISSING COUNTERSPACE GFI |
| | RECEPT. 210.52C1 |
| | SEE CIRCUITING, REDLINED. |
| | |
| | 10)NOTE: PLEASE SEE ALL RECEPTS SERVING |
| | KITCHEN/KITCHEN AREA COUNTERSPACE ARE TO |
| | BE GFI/GFI PROTECTED. |
| | |
| | 11)NOTE: PLEASE INDICATE THE KW RATINGS |
| | FOR AHU'S AND HEAT BEING USED FOR LOAD |
| | CALCS. |
| | 215.5. |
| | |
| | 12)NOTE: PLEASE SEE PANEL "B" WHICH |
| | INDICATES A SEPARATE OVEN AND A SEPRATE |
| | RANGE, HOWEVER LOAD CALCS SEEMT O ONLY |
| | SHOW 8KW FOR BOTH UNITS?? |
| | PLEASE VERIFY AND ADJUST AS CIRCUITS |
| | SEEM TO BE FOR MORE THAN 8KW FOR BOTH. |
| | 215.5, 220 |
| | |
| | 13)NOTE: PLEASE SEE AN EQUIPMENT |
| | GROUNDING CONDUCTOR IS STILL BEING SHOWN |
| | FROM METER TO THE FIRST MEANS OF |
| | DICCONNECT. PLEASE SEE 250.6, 250.24 THE |
| | "EQUIPMENT GROUNDING CONDUCTOR" IS ONLY |
| | INSTALLED "AFTER" THE FIRST MEANS OF |
| | DISCONNECT. |
| | |
| | PLEASE BE SURE TO CORRELATE ALL |
| | CIRCUITING ON PLANS WITH PANEL |
| | SCHEDULES. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW AND STAMPING. IF THERE ARE ANY |
| | QUESTIONS, PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS OFFICE. |
| | |