Plan Review Notes
Plan Review Notes For Permit 02101307
Permit Number 02101307
Review Stop E
Sequence Number 9
Notes
Date Text
2006-01-20 00:00:00************ UNSAT ************
  
  
 1)NOTE: PLEASE CORRELATE ALL CIRCUITING
 ON PLANS WITH PANEL SCHEDULES.
 PLEASE SEE LTS ON SMALL APPL, LTS ON
 DRYER, BATHS, KIT, APPLIANCES, ETC ETC.
 PLEASE SEE THERE ARE FAR TOO MANY TO
 WRITE UP OR REDLINE. PLEASE SEE MANY OF
 THESE WERE REDLINED, HOWEVER BY NO MEANS
 ALL.
  
 2)NOTE: PLEASE SEE SMOKE DETECTORS'S
 SHOWN ON THREE OR MORE CIRCUITS. PLEASE
 SEE NFPA-72 8-1 WHICH REQUIRES SD'S TO
 BE WIRED "IN-LINE". IF WIRED IN-LINE,
 THEN THESE CAN NOT BE ON MORE THAN ONE
 CIRCUIT. ALSO SHOWN ON MULTIPLE PANELS.
  
 3)NOTE: PLEASE SEE 210.52D,210.11C3,
 WHICH REQUIRES ALL BATH(S) CIRCUIT(S)
 RECEPTS TO BE ON A MIN OF 20A AND #`12.
 PLEASE SEE CIRCUITING AS MANY ARE SHOWN
 ON OTHER CIRCUITS WHICH ARE 15A AND #14
 AWG.
  
 4)NOTE: PLEASE CORRELATE ALL POOL
 EQUIPMENT ON PLANS WITH PANEL SCHEDULES
 AND LOAD CALCUALTIONS. PLEASE SEE
 CIRCUITING ON PLANS IS ALSO SHOWN AS
 COND UNITS.??
 PLEASE SEE PLANS SHOW TWO ELEC POOL
 HEATERS, HOWVER PANEL SCHEDULE SHOWS
 ONE??
 PLEASE ALSO SEE ALL CONTINUOUS LOADS
 SUCH AS POOL HEATER AND POOL PUMP SHALL
 BE SHOWN AT 125%. 215.3,230.42,
 PLEASE SEE MIN OCP SHALL BE SIZED AT
 125% PER 680.9. PLEASE PROVIDE KW
 RATINGS FOR POOL HEATERS.
  
 5)NOTE: PLEASE SEE PLANS, CLEARENCES FOR
 CU DISCONNNECTS DO NOT MEET 110.26.
 PLEASE ALSO SEE ANY AHU'S WHICH APPEAR
 TO SHOW SHELVING DIRECTLY INFRONT OF
 THESE DISCONNECTS AND UNITS.
  
 6)NOTE: PLEASE SEE CORRELATE PANEL
 SCHEDULES AND RISER DIAGRAM. PLEASE SEE
 ALL PANELS INDICATE MAINS (A
 GARAGE PANEL REQUIRED) HOWEVER PANELS
 FOR POOL PANEL AND PANEL C SHOWS MLO ON
 SCHEDULE AND SHOWS MAIN DISCONNECT ON
 RISER?? PLEASE CORRELATE.
 215.5
  
 7)NOTE: PLEASE SEE PLANS SHOWS POOL
 PANEL AND A PANEL "D"??
 PLEASE CORRELATE.215.5
  
 8)NOTE: PLEASE SEE CIRCUITS SHOWN ON
 PLANS AS GEN LTS, PELASE SEE CIRCUITING
 SHALL BE SPECIFIC TO AREA/ROOMS.
 215.5, 408.4
  
 9)NOTE: PLEASE SEE KITCHEN AREA WHERE
 APPEARS TO BE A MISSING COUNTERSPACE GFI
 RECEPT. 210.52C1
 SEE CIRCUITING, REDLINED.
  
 10)NOTE: PLEASE SEE ALL RECEPTS SERVING
 KITCHEN/KITCHEN AREA COUNTERSPACE ARE TO
 BE GFI/GFI PROTECTED.
  
 11)NOTE: PLEASE INDICATE THE KW RATINGS
 FOR AHU'S AND HEAT BEING USED FOR LOAD
 CALCS.
 215.5.
  
 12)NOTE: PLEASE SEE PANEL "B" WHICH
 INDICATES A SEPARATE OVEN AND A SEPRATE
 RANGE, HOWEVER LOAD CALCS SEEMT O ONLY
 SHOW 8KW FOR BOTH UNITS??
 PLEASE VERIFY AND ADJUST AS CIRCUITS
 SEEM TO BE FOR MORE THAN 8KW FOR BOTH.
 215.5, 220
  
 13)NOTE: PLEASE SEE AN EQUIPMENT
 GROUNDING CONDUCTOR IS STILL BEING SHOWN
 FROM METER TO THE FIRST MEANS OF
 DICCONNECT. PLEASE SEE 250.6, 250.24 THE
 "EQUIPMENT GROUNDING CONDUCTOR" IS ONLY
 INSTALLED "AFTER" THE FIRST MEANS OF
 DISCONNECT.
  
 PLEASE BE SURE TO CORRELATE ALL
 CIRCUITING ON PLANS WITH PANEL
 SCHEDULES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW AND STAMPING. IF THERE ARE ANY
 QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]